Customer Class File Number
ERICO International Corporation
34600 Solon Rd
Solon
Ohio
United States
44139
5851-01
WIRES - Appliance
090005_0_000

TO THE REQUIREMENTS OF CSA STANDARD C22.2 NO. 210-15:


FLEXIBLE INSULATED BUSBAR TYPE ERIFLEX FLEXIIBAR

AWM
Class
AWM
Group
Temp
Rating
(C)
Voltage
Rating
(V)
Insul. Type
Min. Avg.Thick.
(mm)
Notes
I A/B 105 Dry
75 Wet
1000  PVC /1.07 1, 2, 3, 4
           
           
FLEXIBLE INSULATED BUSBAR TYPE ERIFLEX FLEXIIBAR ADVANCED
           
AWM
Class
AWM
Group
Temp
Rating
(C)
Voltage
Rating
(V)
Insul. Type
Min. Avg.Thick.
(mm)
Notes
I A/B 60/80/90/105Dry/115Dry 30/150/300/6001000 TPE/1.52 1, 2, 4, 8, 9, 10

*Number of laminates times width of laminate (mm) times thickness of laminates (mm).

INSULATED BRAIDED CONDUCTOR (IBS, IBSB/IBSBR)

AWM
Class
AWM
Group
Temp
Rating
(C)
Voltage
Rating
(V)
Insul. Type
Min. Avg. Thick.
(mm)
Notes
I A/B 105 Dry
75 Wet
1000  PVC (1.07mm)  3, 4, 5, 6, 7
           
INSULATED BRAIDED CONDUCTOR (IBS, IBSB/IBSBR ADVANCED)
AWM
Class
AWM
Group
Temp
Rating
(C)
Voltage
Rating
(V)
Insul. Type
Min. Avg. Thick.
(mm)
Notes
I A/B 60/80/90/105Dry/115Dry 30/150/300/6001000 TPE/1.52  4, 5, 6, 7, 8, 9,10


Notes:  For specific details see certification report.

  1. The insulated busbars supplied in lengths of up to 4 meters.
  2. Conductor composition consists of 2-12 laminates (tinned or bare copper or nickel coated) with each strip having a thickness of 0.5mm/0.8mm/1.0mm and a width of 9mm-120mm.
  3. PVC insulated (black colour only).
  4. Flame classification: FT1.
  5. The Insulated Braided Conductors supplied in lengths from 230mm to 5000mm.
  6. Conductors consist of braided strands 0.15mm in diameter (tinned or bare copper or nickel coated) with cross sections of 25mm2 to 240mm2
  7. Flat or Round construction.
  8. Flame classification FT2.
  9. Flame classification VW-1.
  10. All colours except clear and translucent.