Class Number Description
5411-06
TRANSFORMERS - Power

COVERAGE:

Dry type transformers, enclosed types, for indoor and outdoor applications, open core and
coil assemblies and single-phase, polyphase multi-winding and auto-transformers.

This category does not include certain special transformers, transformers for
luminous-tube signs, oil- or gas-burner ignition, cold-cathode interior lighting,
electronic or liquid-filled designs.

REQUIREMENTS:

CSA C22.2 No 0-M General Requirements – Canadian Electrical Code, Part II
CSA C22.2 No 0.4 Bonding of Electrical Equipment
CSA C22.2 No 47 Air-Cooled Transformers (Dry-Type)
CSA C22.2 No 66 Specialty Transformers – Industrial Products
CSA C22.2 No. 66.1 Low Voltage Transformers
– Part 1: General Requirements
CSA C22.2 No. 66.2 Low Voltage Transformers
– Part 2: General Purpose Transformers
CSA C22.2 No. 66.3 Low Voltage Transformers
– Part 3: Class 2 and Class 3 Transformers
CSA C22.2 No 94 Special Purpose Enclosures – Industrial
Products
CSA C22.2 No 180 Series Isolating Transformers for Airport Lighting

NOTE:  Open core and coil transformers are Certified as components for
installation in an enclosure of other Certified electrical equipment and subject to
further investigation by CSA International. Electrical spacings on component type
transformers in the areas outside the coils may not have been assessed. The suitability of
electrical spacings in these areas must be assessed to CSA Standard C22.2 No 66 or
CSA Standard C22.2 No 66.x Series or to the
Standard applicable in the end use equipment.

MARKING:

  • submittor's identification;
  • model designation or equivalent;
  • complete electrical rating;
  • CSA Enclosure type where applicable;
  • date code or equivalent;
  • additional markings as may be required;
  • CSA Mark.