Customer Class File Number
Chromalox, Inc.
2150 North Rulon White Blvd
Ogden
Utah
United States
84404
2878-82
HEATERS-Miscellaneous - For Hazardous Locations-Certified to U.S. Standards
207901

Last Updated:

November 27, 2018 (Replaces: November 7, 2014)


Class I, Groups B, C and D; Class II, Groups E, F and G, Class I Zone 1 Ex d IIB, AEx d IIB:

Immersion heaters, screw plug type, with thermostat, with or without thermocouple, Series MT, EMT, and TM-1 without thermostat, with or without thermocouple, single or three phase.

ModelsVoltage (VAC max)Power (kW max)Max. Watts Density (W/sq-in)
ARMT, AREMT, ARTM, MT, EMT, TM-16002590

Series may include suffix C32, C33, C34, C35, E2, E3, I, II, IS, M, O, OIS, OS, OSS, S, SS, T, V, W, WI, WS, WSS, XX. Series may include suffix A, 3 or 3A. ARMT and AREMT Series may include suffix T1, T2, T3, T4, T5 or T8. ARTM Series may include suffix TL or TH.

Note:
Enclosures built to the specifications of Figures 32-38, size range from 3? to 16? flange (flat lid) are suitable for Class I, Groups B, C and D; Class II, Groups E, F and G, Class I, Zone 1 Ex d IIB+H2, AEx d IIB+H2. Flanges 18? and higher are suitable only for Gas Group IIB.

 

Immersion heaters, screw plug type, with or without thermostat, with or without thermocouple or RTD, single or three phase. May include suffix A, S, C, T1, T2, T2R, T3, M6, M7, X.

K

ModelsVoltage (VAC max)Max. Watts Density (W/sq-in)
Ogden60090

Note:
Enclosures built to the specifications of Figures 32-38, size range from 3? to 16? flange (flat lid) are suitable for Class I, Groups B, C and D; Class II, Groups E, F and G, Class I, Zone 1 Ex d IIB+H2, AEx d IIB+H2. Flanges 18? and higher are suitable only for Gas Group IIB.

Immersion heaters, tank type, with or without thermostat, single or three phase. May include suffix A, C, ER, I, O, S, T1, T2, T3, V, W, XX.

ModelsVoltage (VAC max)Max. Watts Density (W/sq-in)Power (kW max)
TL, KTL6005025

Note:
Enclosures built to the specifications of Figures 32-38, size range from 3? to 16? flange (flat lid) are suitable for Class I, Groups B, C and D; Class II, Groups E, F and G, Class I, Zone 1 Ex d IIB+H2, AEx d IIB+H2. Flanges 18? and higher are suitable only for Gas Group IIB.

 

Immersion heaters, flange type, with or without thermostat, with or without thermocouple, single or three phase. May include suffix A, B, C32, C33, C34, C35, C42, C43, C44, C45, E2, E3, F, F1, H, I, II, IS, L, M, O, R1, S, SS, SSS, T, T1, T2, T3, V, W, XX.

ModelsVoltage (VAC max)Max. Watts Density (W/sq-in)
TM60090

Note:
Enclosures built to the specifications of Figures 32-38, size range from 3? to 16? flange (flat lid) are suitable for Class I, Groups B, C and D; Class II, Groups E, F and G, Class I, Zone 1 Ex d IIB+H2, AEx d IIB+H2. Flanges 18? and higher are suitable only for Gas Group IIB.

Immersion heaters, flange type, with or without thermostat, with or without thermocouple or RTD. May include suffix A, S, C, T1, T2, T2R, T3, M6, M7, X.

ModelsVoltage (VAC max)Max. Watts Density (W/sq-in)Phase
Ogden Series K60090single or three

Notes:

  1. The Certification is conditional on the provision of an approved liquid level and/or temperature limiting control and/or pressure control which will de-energize the heater in the event of system malfunctions.
  2. The overall hazardous location designation is governed by the device with the lowest hazardous location rating.
  3. The max surface temperature of exposed element or enclosure housing must not exceed the following:
    Class I, Groups B, C, and D: T1 0 T6
    Class II, Groups E and F: 200� C (T3)
    Class II, Groups G: 165�C (T3B)
    Class I, Zone I Ex d IIB & AEx d IIB: T1 - T6
  4. Enclosures built to the specifications of Figures 53-64 are suitable for Class I, Groups B, C and D; Class II, Groups E, F and G, Class I Zone 1 Ex d IIB+H2, AEx d IIB+H2.

Circulation heaters, with or without thermostat, with or without thermocouple, NWH Series may include suffix A, B, F, I, II, IS, M , O, OIS, R, S, SS, SSS, SSMT, T. GCH Series may include suffix A, B, IS, S, SS, SSS. NWH and GCH Series may include suffix C22, C23, C32, C33, C34, C35, C42, C43, C44, C45, E2, E3, V, W, XX, T1, T2, T3, T10, T12 and T13.

Ogden

ModelsVoltage (VAC max)PhaseMax. Watts Density (W/sq-in)
NWH, GCH600single or three90and, 25 w/sq in max respectively

Notes:

  1. The Certification is conditional on the provision of an approved liquid level and/or temperature limiting control and/or pressure control which will de-energize the heater in the event of system malfunctions.
  2. The overall hazardous location designation is governed by the device with the lowest hazardous location rating.
  3. The max surface temperature of exposed element or enclosure housing must not exceed the following:
    Class I, Groups B, C, and D: T1 0 T6
    Class II, Groups E and F: 200� C (T3)
    Class II, Groups G: 165�C (T3B)
    Class I, Zone I Ex d IIB & AEx d IIB: T1 - T6
  4. Enclosures built to the specifications of Figures 53-64 are suitable for Class I, Groups B, C and D; Class II, Groups E, F and G, Class I Zone 1 Ex d IIB+H2, AEx d IIB+H2.

 

Circulation heaters, with or without thermostat, with or without thermocouple or RTD, may include suffix A, S, C, M6, M7, X and prefix A.

ModelsVoltage (VAC max)PhaseMax. Watts Density (W/sq-in)
CK600single or three90

Notes:

  1. The Certification is conditional on the provision of an approved liquid level and/or temperature limiting control and/or pressure control which will de-energize the heater in the event of system malfunctions.
  2. The overall hazardous location designation is governed by the device with the lowest hazardous location rating.
  3. The max surface temperature of exposed element or enclosure housing must not exceed the following:
    Class I, Groups B, C, and D: T1 0 T6
    Class II, Groups E and F: 200� C (T3)
    Class II, Groups G: 165�C (T3B)
    Class I, Zone I Ex d IIB & AEx d IIB: T1 - T6
  4. Enclosures built to the specifications of Figures 53-64 are suitable for Class I, Groups B, C and D; Class II, Groups E, F and G, Class I Zone 1 Ex d IIB+H2, AEx d IIB+H2.

 

Circulation heaters, with or without thermostat, with or without thermocouple, may include suffixes, E2, XX.

ModelsVoltage (VAC max)PhaseMax. Watts Density (W/sq-in)
Series SHO600single or three5 respectively

Notes:

  1. The Certification is conditional on the provision of an approved liquid level and/or temperature limiting control and/or pressure control which will de-energize the heater in the event of system malfunctions.
  2. The overall hazardous location designation is governed by the device with the lowest hazardous location rating.
  3. The max surface temperature of exposed element or enclosure housing must not exceed the following:
    Class I, Groups B, C, and D: T1 0 T6
    Class II, Groups E and F: 200� C (T3)
    Class II, Groups G: 165�C (T3B)
    Class I, Zone I Ex d IIB & AEx d IIB: T1 - T6
  4. Enclosures built to the specifications of Figures 53-64 are suitable for Class I, Groups B, C and D; Class II, Groups E, F and G, Class I Zone 1 Ex d IIB+H2, AEx d IIB+H2.

 

Flanged type immersion heaters with or without thermostat, with or without thermocouple. STFX may include suffix I, S, X, E2 and XX.

ModelsPhaseVoltage (V)Max. Watts Density (W/sq-in)
STFXsingle or three600 or less90

Notes:

  1. The Certification is conditional on the provision of an approved liquid level and/or temperature limiting control and/or pressure control which will de-energize the heater in the event of system malfunctions.
  2. The overall hazardous location designation is governed by the device with the lowest hazardous location rating.
  3. The max surface temperature of exposed element or enclosure housing must not exceed the following:
    Class I, Groups B, C, and D: T1 0 T6
    Class II, Groups E and F: 200� C (T3)
    Class II, Groups G: 165�C (T3B)
    Class I, Zone I Ex d IIB & AEx d IIB: T1 - T6
  4. Enclosures built to the specifications of Figures 53-64 are suitable for Class I, Groups B, C and D; Class II, Groups E, F and G, Class I Zone 1 Ex d IIB+H2, AEx d IIB+H2.

 

LTFX Large Tank Flange Immersion Heater

ModelsVoltage (V)Power (kW max)
LTFX Large Tank Flange Immersion Heater600 or less240

Note:

Cat. No. Nomenclature:

LTFX         3      3       25      90      E2     XX                - optional -     48      3     90

/mr