C22.2 NO. 184.1-96 (R2011)
Solid-State Dimming Controls (Bi-National standard, with UL 1472)
détails du produit
1.1
These requirements cover permanently installed devices, hereafter referred to as dimmers, that employ a dimming function intended for control of lighting loads of the ballast, transformer, or tungsten-filament type, and are intended to be installed in a wallbox or are provided with an enclosure for flush or surface mounting in accordance with the Canadian Electric Code, Part 1 (CEC), and the National Electrical Code (NEC), ANSI/NFPA 70.
1.2
These requirements cover devices, other than touch dimmers, rated 600 volts ac or less, and touch dimmers rated 120 volts ac or less, all for installation on a 20-ampere or less branch circuit.
1.3
These requirements cover dimmers, including touch dimmers, having a minimum power rating of 300 W or 300 volt-amperes, and a maximum power rating of 2000 W or 2000 volt-amperes in increments of 50 watts or 50 volt-amperes.
1.4
A device incorporating other functions (for example, speed control) in addition to a dimming function is investigated on the basis of compliance with the applicable requirements for the dimming function in this Standard as well as requirements for the other functions in the applicable standards.
1.5
These requirements do not cover dimmers that use only a resistor or a transformer to perform the dimming function.
1.6
These requirements do not cover modular, cabinet or console type constructions.
1.7
A product that contains features, characteristics, components, materials, or systems new or different from those covered by the requirements in this standard, and that involves a risk of fire, electric shock, or injury to persons shall be evaluated using the appropriate additional component and end-product requirements as determined necessary to maintain the acceptable level of safety as originally anticipated by the intent of this standard. A product whose features, characteristics, components, materials, or systems conflict with specific requirements or provisions of this standard cannot be judged to comply with this standard. Where considered appropriate, revision of requirements shall be proposed and adopted in conformance with the methods employed for development, revision, and implementation of this standard.