Customer Class File Number
Valworx, Inc.
18636 Northline Drive
Cornelius
North Carolina
United States
28031
3221-02
VALVES - General purpose Actuators
267592

To the requirement of Canadian standard CSA C22.2 No. 139

  • Electric valve actuators, Motorized, General purpose, 6,000 cycles, Type 4X Enclosure, ambient temperature -25 to 55 Deg C,

Models

Volt

Hz

A

Torque [N-m]

Duty cycle

Operating Time [s]

Signal Input

Signal Output

VDC

mA

VDC

mA

561701

110 Vac

50/60

0.30

16

60%

15/12

--

--

--

--

561702

24 Vac

50/60

1.56

16

60%

15/12

--

--

--

--

561703

220 Vac

50/60

0.19

16

60%

15/12

--

--

--

--

561704

24 Vdc

--

0.70

16

60%

15

--

--

--

--

561705

24 Vdc

--

0.70

16

60%

15

--

--

--

--

561706

24 Vdc

--

0.70

16

60%

15

--

--

--

--

561708

110 Vac

50/60

0.30

16

60%

15/12

0-10

4-20

24

4-20

561825C

110 Vac

50/60

0.27

30

70%

12/10

--

--

--

--

561850C

110 Vac

50/60

0.27

50

70%

25/21

--

--

--

--

561851C

24 Vdc

--

1.28

50

70%

25

--

--

--

--

561853C

24 Vac

50/60

1.56

50

70%

25/21

--

--

--

--

561854C

220 Vac

50/60

0.19

50

70%

25/21

--

--

--

--

561856C

110 Vac

50/60

0.27

50

70%

25/21

0-10

4-20

24

4-20

561857C

24 Vdc

--

1.28

50

70%

25

0-10

4-20

24

4-20

561857A

24 Vdc

--

1.0

50

70%

30

0-10

4-20

24

4-20

561862A

110 Vac

50/60

0.64

100

70%

30/25

--

--

--

--

561863A

110 Vac

50/60

0.64

100

70%

30/25

0-10

4-20

24

4-20

561865A

24 Vdc

--

2.03

100

70%

30

--

--

--

--

561867C

24 Vdc

--

2.03

100

70%

30

0-10

4-20

24

4-20

561867A

24 Vdc

--

1.8

100

70%

30

0-10

4-20

24

4-20

561870A

110 Vac

50/60

0.73

200

70%

30/25

--

--

--

--

561871A

24 Vdc

--

3.57

200

70%

30

--

--

--

--

561877C

24 Vdc

--

3.57

200

70%

30

0-10

4-20

24

4-20

561876A

110 Vac

50/60

0.73

200

70%

30/25

0-10

4-20

24

4-20

561877A

24 Vdc

--

1.70

200

70%

30

0-10

4-20

24

4-20

561885A

110 Vac

50/60

1.22

400

70%

30/25

--

--

--

--

561886A

110 Vac

50/60

1.22

400

70%

30/25

0-10

4-20

24

4-20

561887A

24 Vdc

--

3.55

400

70%

30

0-10

4-20

24

4-20

561887C

24 Vdc

--

5.13

400

70%

30

0-10

4-20

24

4-20

561888A

24 Vdc

--

5.13

400

70%

30

--

--

--

--

561895A

110Vac

50/60

1.27

600

70%

45/37

--

--

--

--

561896A

110Vac

50/60

1.27

600

70%

45/37

0-10

4-20

24

4-20

561951A

110Vac

50/60

2.39

1000

70%

30/25

--

--

--

--

561956A

110Vac

50/60

2.39

1000

70%

30/25

0-10

4-20

24

4-20

561961A

110Vac

50/60

2.36

1600

70%

48/40

--

--

--

--

561966A

110Vac

50/60

2.36

1600

70%

48/40

0-10

4-20

24

4-20

561971A

110Vac

50/60

2.46

2500

70%

75/63

--

--

--

--

561976A

110Vac

50/60

2.46

2500

70%

75/63

0-10

4-20

24

4-20

Notes:

1. Suffix may be added for features not affecting certification.

2. Signal input terminals are intended to be connected to a Class 2 circuit only.

3. Certified only as a component of other certified equipment, where the suitability of the combination is to be determined.