Customer Class File Number
ALTENERGY POWER SYSTEM INC.
Building 2, No. 522 Yatai Road
Nanhu District
Jiaxing City
Zhejiang
China
314050
5311-89
POWER SUPPLIES - Distributed Generation - Power Systems Equipment - Certified to U.S. Standards
259077

To the requirements of
UL 1741 (Second Edition)

P Grid Support Utility Interactive Microinverter, Rack mounted

Model(s)
YC600

Model:

YC600

 

 

 

INPUT RATINGS:

 

Maximum input voltage

55V dc

 

Range of input operating voltage

16-55V dc

 

Range of MPPT input operating voltage

22 -45 V dc

 

Maximum input string

2

 

Maximum input current (dc)

12 A ¡Á 2

 

Maximum input short circuit current

13.2A

 

Maximum input sourcebackfeed current to input source

0 A

 

OUTPUT RATINGS:

 

Output power factor rating

>0.99

 

Operating voltage range (ac)1

211.2-264V ac

 

Operating frequency range or single frequency1

59.3-60.5 Hz

 

Number of phases

 

Nominal output voltage (ac)

240V ac

 

Normal output frequency

60 Hz

 

Maximum continuous output current (ac)

2.28A

 

Maximum continuous output power (ac)

548VA

 

Maximum output fault current (ac) and duration

170Apk, 0.36ms of duration, 3.98Arms, over 3 cycles

 

Maximum output overcurrent protection

6.3A

 

Utility interconnection voltage and frequency trip limits and trip times

See Note 1 below

 

Trip limit and trip time accuracy

Voltage:

+/- 2VL-N

 

Frequency:

+/- 0.1Hz

 

Alternate Trip Time

See Note 1 below.

 

Normal operation temperature range

-40ºC - +65ºC

 

Maximum operating ambient

+65ºC

 

Enclosure Rating Type

Type 6

 

 

 

 

 

 

 

 

 

 

 

Notes:

1.Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60Hzabefore cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50Vnor

Rated

0.08

+/-80ms

ZB

0.75Vnor<= V < 0.995Vnor

Rated

0.16 - 600

+/-200ms

C

1.004Vnor< V < 1.125Vnor

Rated

0.16 - 600

+/-200ms

D

1.20Vnor<=V

Rated

0.08

+/-80ms

E

60.1<f <62.0

f > 60.5

0.08~600

+/-200ms

F

57.0<f <59.9

f < 59.3

0.08~600

+/-200ms

Reconnection time accuracy: 30-600S  +/-10s

  1. Utility interactive evaluations were conducted with the following firmware:

Inverter Model

MICROPROCESSOR/FPGA

FIRMWARE

CHECKSUM

YC600

LFE3-35EA-6FTN256C

V7

0415DBAB

  1. Surge Testing for Combination Wave (1.2/50us) was done at 6 kV/3 kA, 2 ohms effective impedance, andRingwave (0.5us-100 kHz) was done at 6 kV/0.5 kA, 12 ohms effective impedance.  Tests were performed using both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.
  2. This product's software has not been evaluated to the requirements of UL 1998.
  3. Model YC600 was evaluated to meet the California Rule 21 grid support functions according to UL 1741 Supplement SA8-SA18.
  4. Grid Support Utility Interactive PV Inverter, Model YC600 was evaluated with reactive power priority in UL 1741SA 13 Volt/Var Mode (Q(V)) Test.

Model(s)
QS1200, QS1, QS1A

Models rating as follows:      

Model:

QS1

QS1200

QS1A

INPUT RATINGS:

Maximum input voltage

60V dc

60V dc

60V dc

Range of input operating voltage

16-55 V dc

16-55 V dc

16-55 V dc

Range of MPPT input operating voltage

22 - 48 V dc

22 - 48 V dc

30 - 52 V dc

Maximum input string

4

4

4

Maximum input current (dc)

12 A (4 inputs)

12 A (4 inputs)

13.3 A (4 inputs)

Maximum input short circuit current

15A per input

15A per input

15A per input

Maximum input source backfeed current to input source

0 A

0 A

0 A

OUTPUT RATINGS:

 

 

Output power factor rating

>0.99 (-0.8 ~ 0.8 adjustable)

>0.99 (-0.8 ~ 0.8 adjustable)

>0.99 (-0.8 ~ 0.8 adjustable)

Operating voltage range (ac) 1

211.2 - 264Vac for 240Vac output;

183.04 - 228.8Vac for 208Vac output.

211.2 - 264Vac

211.2 - 264V ac

Operating frequency range or single frequency1

59.3 - 60.5 Hz

59.3 - 60.5 Hz

59.3 - 60.5 Hz

Number of phases

Nominal output voltage (ac)

240Vac/ 208Vac

240 Vac

240 Vac

Normal output frequency

60 Hz

60 Hz

60 Hz

Maximum continuous output current (ac)

5A for 240Vac; 5.77A for 208Vac

5A

6.25A

Maximum continuous output power (ac)

1200VA

1200VA

1500VA

Maximum output fault current (ac) and duration

137 Apk, duration 0.78ms, 39.94 Arms

137 Apk, duration 0.78ms, 39.94 Arms

47.3Apeak, duration 1.4ms, 4.68Arms

Maximum output overcurrent protection

10A

10A

16A

Utility interconnection voltage and frequency trip limits and trip times

See Note 1 below

See Note 1 below

See Note 1 below

Trip limit and trip time accuracy

Voltage:

+/- 2VL-L

Frequency:

+/- 0.1 Hz

Alternate Trip Time

See Note 1 below.

Normal operation temperature range

-40ºC - + 65ºC

Maximum operating ambient

+65ºC

Enclosure Rating Type

Type 6

Notes:

  1. Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50 Vnor

Rated

0.08

+/-80ms

B

0.75 Vnor <=V < 0.995 Vnor for 240Vac output

(adjustable)

0.865Vnor<=V < 0.995 Vnor for 208Vac output

(adjustable)

Rated

0.16 - 600

+/-200ms

C

1.004 Vnor< V < 1.125 Vnor

(adjustable)

Rated

0.16 - 600

+/-200ms

D

1.20 Vnor <=V

Rated

0.08

+/-80ms

E

60.1<f <62.0

(adjustable)

f > 60.5

0.08 - 600

+/-200ms

F

57.0<f <59.9

(adjustable)

f < 59.3

0.08 - 600

+/-200ms

Reconnection time accuracy: 30-600S   +/-10s

  1. Utility interactive evaluations were conducted with the following firmware:

Inverter Model

Microprocessor/FPGA

Firmware

Checksum

QS1200

QS1

LFE3-35EA-6FTN256C

V5

E47AAEB8

QS1A

LFE3-35EA-6FTN256C

V7

F6B2A505

  1. Surge Testing for Combination Wave (1.2/50us) was done at 6 kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100 kHz) was done at 6 kV/0.5 kA, 12 ohms effective impedance. Tests were performed using both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.
  2. This product's software has not been evaluated to the requirements of UL 1998.
  3. Model QS1200 and QS1 with 240Vac share the same construction, hardware and software, and only difference between those two models are the model name and output voltage, which are only for commercial purpose.
  4. Models QS1200 and QS1 were evaluated to meet the California Rule 21 grid support functions according to UL 1741 Supplement SA8~SA18.
  5. Model QS1A was evaluated to meet the California Rule 21 grid support functions according to UL 1741 Supplement SA8-SA15.
  6. Grid Support Utility Interactive PV Inverter, Models QS1200, QS1 and QS1A were evaluated with reactive power priority in UL 1741SA 13 Volt/Var Mode (Q(V)) Test.

Utility Interactive Microinverter, Rack mounted

Model(s)
YC600B

  • ratings as follows:

Model:

YC600B

 

 

 

INPUT RATINGS:

 

Maximum input voltage

60V dc

 

Range of input operating voltage

16-60 V dc

 

Range of MPPT input operating voltage

22 - 48 V dc

 

Maximum input string

2

 

Maximum input current (dc)

12 A (2 inputs)

 

Maximum input short circuit current

13.2A per input

 

Maximum input source backfeed current to input source

0 A

 

OUTPUT RATINGS:

 

Output power factor rating

>0.99

 

Operating voltage range (ac) 1

105.6 - 132V ac

 

Operating frequency range or single frequency1

59.3 - 60.5 Hz

 

Number of phases

 

Nominal output voltage (ac)

120 V ac

 

Normal output frequency

60 Hz

 

Maximum continuous output current (ac)

4.57A

 

Maximum continuous output power (ac)

548W

 

Maximum output fault current (ac) and duration

43.3 Apk, duration 3.08 ms , 3.42 Arms

 

Maximum output overcurrent protection

10A

 

Utility interconnection voltage and frequency trip limits and trip times

See Note 1 below

 

Trip limit and trip time accuracy

Voltage:

+/- 2VL-N

 

Frequency:

+/- 0.1 Hz

 

Alternate Trip Time

See Note 1 below.

 

Normal operation temperature range

-40ºC - + 65ºC

 

Maximum operating ambient

+65ºC

 

Enclosure Rating Type

Type 6

 

 

 

 

 

 

 

 

 

 

 

Notes:

1.Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50 Vnor

Rated

0.08

+/-80ms

B

0.75 Vnor <=V < 0.992 Vnor

(adjustable)

Rated

0.16 - 610

+/-200ms

C

1.008 Vnor< V < 1.192 Vnor

(adjustable)

Rated

0.16 - 610

+/-200ms

D

1.20 Vnor <=V

Rated

0.08

+/-80ms

E

60.1<f <62.0

(adjustable)

f > 60.5

0.08 - 610

+/-200ms

F

57.0<f <59.9

(adjustable)

f < 59.3

0.08 - 610

+/-200ms

Reconnection time accuracy: 30-610s(adjustable)  +/-10s

1.Utility interactive evaluations were conducted with the following firmware:

Inverter Model

Microprocessor/FPGA

Firmware

Checksum

YC600B

LFE3-35EA-6FTN256C

V1

8DE26380

1.Surge Testing for Combination Wave (1.2/50us) was done at 6 kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100 kHz) was done at 6 kV/0.5 kA, 12 ohms effective impedance. Tests were performed using both polarities, for common mode and differential mode coupling, 20 pulses each test. After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.

1.This product's software has not been evaluated to the requirements of UL 1998.

To the requirements of
UL 1741 (Third Ed

Model(s)
DS3D, DS3D-MX

Models rating as follow:

 

Model:

DS3D

DS3D-MX

INPUT RATINGS:

 

Maximum input voltage

120Vdc

Range of input operating voltage

52-120Vdc

Range of MPPT input operating voltage

59-90Vdc

Maximum input string

2

Maximum input current (dc)

20A (2 inputs)

Maximum input short circuit current

25A per input

Maximum input source backfeed current to input source

0 A

OUTPUT RATINGS:

 

Output power factor rating

>0.99

Operating voltage range (ac) 1

211.2 - 264Vac

Operating frequency range or single frequency1

59.3 - 60.5 Hz

Number of phases

Nominal output voltage (ac)

240Vac

Normal output frequency

60 Hz

Maximum continuous output current (ac)

8.3A

Maximum continuous output power (ac)

2000W

Maximum output fault current (ac) and duration

17.52Apk, 12.72ms of duration

Maximum output overcurrent protection

16A

Utility interconnection voltage and frequency trip limits and trip times

See Note 1 below

Trip limit and trip time accuracy

Voltage:

+/- 2VL-L

Frequency:

+/- 0.1 Hz

Alternate Trip Time

See Note 1 below.

Normal operation temperature range

-40ºC - +65ºC

Maximum operating ambient

+65ºC

Enclosure Rating Type

Type 6

 

Notes: 

 

  1. Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

 

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50 Vnor

Rated

0.08

+/-80ms

B

0.75Vnor ¡Ü V< 0.995Vnor

Rated

0.16-600

+/-200ms

C

1.004Vnor< V < 1.125 Vnor

Rated

0.16-600

+/-200ms

D

1.20 Vnor ¡Ü V

Rated

0.08

+/-80ms

E

60.1<f<62.0(adjustable)

f > 60.5

0.16

+/-200ms

F

57.0<f<59.9(adjustable)

f < 59.3

0.16

+/-200ms

Reconnection time accuracy: 30-600S +/-10s

 

  1. Utility interactive evaluations were conducted with the following firmware:

Inverter Model

Microprocessor/FPGA

Firmware

Checksum

DS3D

DS3D-MX

TMS320F2800xx

V2

889EFFDD

 

  1. Surge Testing for Combination Wave (1.2/50us) was done at 6 kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100 kHz) was done at 6 kV/0.5 kA, 12 ohms effective impedance. Tests were performed using both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.

 

  1. PV input inverter, models DS3D and DS3D-MX were provided with Photovoltaic (PV) DC Arc-Fault Circuit Protection for series arcing faults.

 

  1. This product's software has not been evaluated to the requirements of UL 1998.

To the requirements of
UL 1741 (Second Edition)

Photovoltaic Rapid Shutdown System Equipment, used to cut off the DC connection of PV modules after the PLC signal lost. Rack mounted. PLC communication used

Model(s)
RSD-D-15-1000, RSD-D-20-1000, RSD-D-25-1000

  • Rating type

    RSD-D-15-1000

    RSD-D-20-1000

    RSD-D-25-1000

    a) Maximum System Voltage

    1000V

    1000V

    1000V

    b) Number of Input Channel

    2

    2

    2

    c) Range of input operating voltage (dc)

    8V-80V for each Channel

    8V-80V for each Channel

    8V-80V for each Channel

    d) Max input current (dc)

    15A for each Channel

    20A for each Channel

    25A** for each Channel

    e) Max Input short circuit current

    25A for each Channel

    25A/38A* for each Channel

    38A for each Channel

    f) Max Output Voltage (dc)

    160V

    160V

    160V

    g) Max Output Current (dc)

    15A

    20A

    25A

    e) Rapid shutdown time limit

    Less than 15s

    Less than 15s

    Less than 15s

    f) Normal operation temperature range

    -40° C - 85°  C

    -40°  C - 85°  C

    -40°  C - 85° C

    g) type of PVRSS or PVRSE (RS1 or RS2)

    RS2

    RS2

    RS2

    h) Enclosure Type

    Type 6P (conform to test requirement)

  • Note

    1. *The different input short current depends on the input cord guage. 4mm2(12 AWG) for 25A; and 6mm2(10 AWG) for 38A.
    2. ** For models RSD-D-25-1500 and RSD-D-25-1000, the maximum input current 25A exists at the input voltage of 65V, while the input voltage exceed 65V, the maximum input current de-rate, the maximum input current will derate to 23.2A while the voltage rise to 70V, and the maximum input current derate to 20.3A while the voltage rise to 80V.
    3. Photovoltaic Rapid Shutdown Function has also been evaluated according to NEC-2017 and NEC-2020 Section 690.12 applicable requirement.

To the requirements of
UL 1741 (Third Ed

Grid Support Utility Interactive Microinverter, rack mounted

Model(s)
DS3-H, DS3, DS3-L, DS3-S

Models rating as follow:

Model:

DS3-H

DS3

DS3-L

DS3-S

INPUT RATINGS:

Maximum input voltage

60Vdc

60Vdc

60Vdc

60Vdc

Range of input operating voltage

26-60Vdc

26-60Vdc

26-60Vdc

26-60Vdc

Range of MPPT input operating voltage

28-45Vdc

28-45Vdc

28-45Vdc

28-45Vdc

Maximum input string

2

2

2

2

Maximum input current (dc)

20A (2 inputs)

20A (2 inputs)

18A (2 inputs)

16A (2 inputs)

Maximum input short circuit current

25A per input

25A per input

22.5A per input

20A per input

Maximum input source backfeed current to input source

0 A

0 A

0 A

0A

OUTPUT RATINGS:

Output power factor rating

>0.99(0.8~0.8

adjustable)

>0.99 (-0.8~0.8 adjustable)

>0.99 (-0.8~0.8 adjustable)

>0.99 (-0.8~0.8 adjustable)

Operating voltage range (ac) 1

211.2 - 264Vac

211.2 - 264Vac

211.2 - 264V ac

211.2 - 264V ac

Operating frequency range or single frequency1

59.3 - 60.5 Hz

59.3 - 60.5 Hz

59.3 - 60.5 Hz

59.3 - 60.5 Hz

Number of phases

Nominal output voltage (ac)

240Vac

240Vac

240Vac

240Vac

Normal output frequency

60 Hz

60 Hz

60 Hz

60Hz

Maximum continuous output current (ac)

4.4A

3.7A

3.2A

2.66A

Maximum continuous output power (ac)

1050VA

880VA

768VA

640VA

Maximum output fault current (ac) and duration

5.691Apk, 26.75ms of duration

5.691Apk, 26.7ms of duration

5.691Apk, 26.75ms of duration

5.691Apk, 26.75ms of duration

Maximum output overcurrent protection

10A

10A

6.3A

6.3A

Utility interconnection voltage and frequency trip limits and trip times

See Note 1 below

See Note 1 below

See Note 1 below

See Note 1 below

Trip limit and trip time accuracy

 

Voltage:

+/- 2VL-L

Frequency:

+/- 0.1 Hz

Alternate Trip Time

See Note 1 below.

Normal operation temperature range

-40ºC - + 65ºC

Maximum operating ambient

+65ºC

Enclosure Rating Type

Type 6

 

Notes: 

 

  1. Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

 

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50 Vnor

Rated

0.08

+/-80ms

B

0.75Vnor ¡Ü V< 0.995Vnor

Rated

0.16-600

+/-200ms

C

1.004Vnor< V < 1.125 Vnor

Rated

0.16-600

+/-200ms

D

1.20 Vnor ¡Ü V

Rated

0.08

+/-80ms

E

60.1<f<62.0(adjustable)

f > 60.5

0.16

+/-200ms

F

57.0<f<59.9(adjustable)

f < 59.3

0.16

+/-200ms

Reconnection time accuracy: 30-600S +/-10s

 

  1. Utility interactive evaluations were conducted with the following firmware:

Inverter Model

Microprocessor/FPGA

Firmware

Checksum

DS3-H

DS3

DS3-L

DS3-S

TMS320F28004x

V3

EBAF651C

 

  1. Surge Testing for Combination Wave (1.2/50us) was done at 6 kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100 kHz) was done at 6 kV/0.5 kA, 12 ohms effective impedance. Tests were performed using both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.
  2. This product's software has not been evaluated to the requirements of UL 1998.
  3. Models DS3-H, DS3, DS3-L and DS3-S were evaluated to meet the California Rule 21 grid support functions according to UL 1741 Supplement SA8-SA18.
  4. Grid Support Utility Interactive PV Inverter, Models DS3-H, DS3, DS3-L and DS3-S were evaluated with reactive power priority in UL 1741SA 13 Volt/Var Mode (Q(V)) Test.

Model(s)
QT2

Models rating as follow:

Model:

QT2

INPUT RATINGS:

 

Maximum input voltage

60Vdc

Range of input operating voltage

26-60Vdc

Range of MPPT input operating voltage

30-45Vdc

Maximum input string

4

Maximum input current (dc)

20A (4 inputs)

Maximum input short circuit current

25A per input

Maximum input source backfeed current to input source

0 A

OUTPUT RATINGS:

 

Output power factor rating

>0.99/0.8 leading...0.8 lagging

Operating voltage range (ac)

183.04 - 228.8Vac

422.4 ¡¡ìC 528Vac

Operating frequency range or single frequency1

59.3 - 60.5 Hz

Number of phases

Nominal output voltage (ac)

208Vac

480Vac

Normal output frequency

60 Hz

Maximum continuous output current (ac)

4.8A*3A

2.17A*3A

Maximum continuous output power (ac)

1728VA

1800VA

Maximum output fault current (ac) and duration

L-L:85.4Apk, 13.6ms of duration, 4.967Arms

L-G:11.4Apk, 20.8ms of duration, 4.543Arms

L-L:35.1Apk, 13.9ms of duration, 2.199Arms

L-G:4.3Apk, 11.5ms of duration, 1.671Arms

Maximum output overcurrent protection

10A*3

6.3A*3

Utility interconnection voltage and frequency trip limits and trip times

See Note 1 below

Trip limit and trip time accuracy

Voltage:

+/- 3VL-L

+/- 4VL-L

Frequency:

+/- 0.1 Hz

Alternate Trip Time

See Note 1 below.

Normal operation temperature range

-40ºC - +65ºC

Maximum operating ambient

+65ºC

Enclosure Rating Type

Type 6

 

 

 

 

 

Notes: 

 

  1. Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

 

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50 Vnor

Rated

0.08

+/-80ms

B

0.833Vnor ¡Ü V< 0.997Vnor

Rated

0.16-600

+/-200ms

B¡¯

0.817Vnor ¡Ü V< 0.995Vnor

Rated

0.16-600

+/-200ms

C

1.002Vnor< V < 1.125Vnor

Rated

0.16-600

+/-200ms

C¡¯

1.004Vnor< V < 1.153Vnor

Rated

0.16-600

+/-200ms

D

1.20 Vnor ¡Ü V

Rated

0.08

+/-80ms

E

60.1<f<62.0(adjustable)

f > 60.5

0.16

+/-200ms

F

57.0<f<59.9(adjustable)

f < 59.3

0.16

+/-200ms

Reconnection time accuracy: 30-600S +/-10s

B and C for 480Vac output voltage and B¡¯ and C¡¯ for 208Vac output voltage.

 

  1. Utility interactive evaluations were conducted with the following firmware:

 

Inverter Model

Microprocessor/FPGA

Firmware

Checksum

480Vac output QT2, QT2-480

TMS320F28x

V3

4593DEF1

208Vac output

QT2, QT2-208

TMS320F28x

V3

B4D0B1F5

 

  1. Surge Testing for Combination Wave (1.2/50us) was done at 6 kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100 kHz) was done at 6 kV/0.5 kA, 12 ohms effective impedance. Tests were performed using both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.

 

  1. Model QT2-208 and QT2 with 208Vac output share the same construction, hardware and software, and only difference between those two models is the model¡¯s name, which is only for commercial purpose.

 

  1. Model QT2-480 and QT2 with 480Vac output share the same construction, hardware and software, and only difference between those two models is the model¡¯s name, which is only for commercial purpose.

 

  1. This product's software has not been evaluated to the requirements of UL 1998.

 

  1. Models QT2-208, QT2-480 and QT2 were evaluated to meet the California Rule 21 grid support functions according to UL 1741 Supplement SA8-SA18.

 

  1. Grid Support Utility Interactive PV Inverter, Models QT2-208, QT2-480 and QT2 were evaluated with reactive power priority in UL 1741SA 13 Volt/Var Mode (Q(V)) Test.

Model(s)
QT2-208

Models rating as follow:

Model:

QT2-208

INPUT RATINGS:

 

Maximum input voltage

60Vdc

Range of input operating voltage

26-60Vdc

Range of MPPT input operating voltage

30-45Vdc

Maximum input string

4

Maximum input current (dc)

20A (4 inputs)

Maximum input short circuit current

25A per input

Maximum input source backfeed current to input source

0 A

OUTPUT RATINGS:

 

Output power factor rating

>0.99/0.8 leading...0.8 lagging

Operating voltage range (ac)

183.04 - 228.8Vac

Operating frequency range or single frequency1

59.3 - 60.5 Hz

Number of phases

Nominal output voltage (ac)

208Vac

Normal output frequency

60 Hz

Maximum continuous output current (ac)

4.8A*3

Maximum continuous output power (ac)

1728VA

Maximum output fault current (ac) and duration

L-L:85.4Apk, 13.6ms of duration, 4.967Arms

L-G:11.4Apk, 20.8ms of duration, 4.543Arms

Maximum output overcurrent protection

10A*3

Utility interconnection voltage and frequency trip limits and trip times

See Note 1 below

Trip limit and trip time accuracy

Voltage:

+/- 3VL-L

Frequency:

+/- 0.1 Hz

Alternate Trip Time

See Note 1 below.

Normal operation temperature range

-40ºC - +65ºC

Maximum operating ambient

+65ºC

Enclosure Rating Type

Type 6

Notes: 

 

  1. Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

 

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50 Vnor

Rated

0.08

+/-80ms

B

0.833Vnor ¡Ü V< 0.997Vnor

Rated

0.16-600

+/-200ms

B¡¯

0.817Vnor ¡Ü V< 0.995Vnor

Rated

0.16-600

+/-200ms

C

1.002Vnor< V < 1.125Vnor

Rated

0.16-600

+/-200ms

C¡¯

1.004Vnor< V < 1.153Vnor

Rated

0.16-600

+/-200ms

D

1.20 Vnor ¡Ü V

Rated

0.08

+/-80ms

E

60.1<f<62.0(adjustable)

f > 60.5

0.16

+/-200ms

F

57.0<f<59.9(adjustable)

f < 59.3

0.16

+/-200ms

Reconnection time accuracy: 30-600S +/-10s

B and C for 480Vac output voltage and B¡¯ and C¡¯ for 208Vac output voltage.

 

  1. Utility interactive evaluations were conducted with the following firmware:

 

Inverter Model

Microprocessor/FPGA

Firmware

Checksum

480Vac output QT2, QT2-480

TMS320F28x

V3

4593DEF1

208Vac output

QT2, QT2-208

TMS320F28x

V3

B4D0B1F5

 

  1. Surge Testing for Combination Wave (1.2/50us) was done at 6 kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100 kHz) was done at 6 kV/0.5 kA, 12 ohms effective impedance. Tests were performed using both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.

 

  1. Model QT2-208 and QT2 with 208Vac output share the same construction, hardware and software, and only difference between those two models is the model¡¯s name, which is only for commercial purpose.

 

  1. Model QT2-480 and QT2 with 480Vac output share the same construction, hardware and software, and only difference between those two models is the model¡¯s name, which is only for commercial purpose.

 

  1. This product's software has not been evaluated to the requirements of UL 1998.

 

  1. Models QT2-208, QT2-480 and QT2 were evaluated to meet the California Rule 21 grid support functions according to UL 1741 Supplement SA8-SA18.

 

  1. Grid Support Utility Interactive PV Inverter, Models QT2-208, QT2-480 and QT2 were evaluated with reactive power priority in UL 1741SA 13 Volt/Var Mode (Q(V)) Test.

Model(s)
QT2-480

Models rating as follow:

Model:

QT2-480

INPUT RATINGS:

 

Maximum input voltage

60Vdc

Range of input operating voltage

26-60Vdc

Range of MPPT input operating voltage

30-45Vdc

Maximum input string

4

Maximum input current (dc)

20A (4 inputs)

Maximum input short circuit current

25A per input

Maximum input source backfeed current to input source

0 A

OUTPUT RATINGS:

 

Output power factor rating

>0.99/0.8 leading...0.8 lagging

Operating voltage range (ac)

422.4 ¡¡ìC 528Vac

Operating frequency range or single frequency1

59.3 - 60.5 Hz

Number of phases

Nominal output voltage (ac)

480Vac

Normal output frequency

60 Hz

Maximum continuous output current (ac)

2.17A*3

Maximum continuous output power (ac)

1800VA

Maximum output fault current (ac) and duration

L-L:35.1Apk, 13.9ms of duration, 2.199Arms

L-G:4.3Apk, 11.5ms of duration, 1.671Arms

Maximum output overcurrent protection

6.3A*3

Utility interconnection voltage and frequency trip limits and trip times

See Note 1 below

Trip limit and trip time accuracy

Voltage:

+/- 4VL-L

Frequency:

+/- 0.1 Hz

Alternate Trip Time

See Note 1 below.

Normal operation temperature range

-40ºC - +65ºC

Maximum operating ambient

+65ºC

Enclosure Rating Type

Type 6

Notes: 

 

  1. Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

 

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50 Vnor

Rated

0.08

+/-80ms

B

0.833Vnor ¡Ü V< 0.997Vnor

Rated

0.16-600

+/-200ms

B¡¯

0.817Vnor ¡Ü V< 0.995Vnor

Rated

0.16-600

+/-200ms

C

1.002Vnor< V < 1.125Vnor

Rated

0.16-600

+/-200ms

C¡¯

1.004Vnor< V < 1.153Vnor

Rated

0.16-600

+/-200ms

D

1.20 Vnor ¡Ü V

Rated

0.08

+/-80ms

E

60.1<f<62.0(adjustable)

f > 60.5

0.16

+/-200ms

F

57.0<f<59.9(adjustable)

f < 59.3

0.16

+/-200ms

Reconnection time accuracy: 30-600S +/-10s

B and C for 480Vac output voltage and B¡¯ and C¡¯ for 208Vac output voltage.

 

  1. Utility interactive evaluations were conducted with the following firmware:

 

Inverter Model

Microprocessor/FPGA

Firmware

Checksum

480Vac output QT2, QT2-480

TMS320F28x

V3

4593DEF1

208Vac output

QT2, QT2-208

TMS320F28x

V3

B4D0B1F5

 

  1. Surge Testing for Combination Wave (1.2/50us) was done at 6 kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100 kHz) was done at 6 kV/0.5 kA, 12 ohms effective impedance. Tests were performed using both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.

 

  1. Model QT2-208 and QT2 with 208Vac output share the same construction, hardware and software, and only difference between those two models is the model¡¯s name, which is only for commercial purpose.

 

  1. Model QT2-480 and QT2 with 480Vac output share the same construction, hardware and software, and only difference between those two models is the model¡¯s name, which is only for commercial purpose.

 

  1. This product's software has not been evaluated to the requirements of UL 1998.

 

  1. Models QT2-208, QT2-480 and QT2 were evaluated to meet the California Rule 21 grid support functions according to UL 1741 Supplement SA8-SA18.

 

  1. Grid Support Utility Interactive PV Inverter, Models QT2-208, QT2-480 and QT2 were evaluated with reactive power priority in UL 1741SA 13 Volt/Var Mode (Q(V)) Test.

Bi‑directional Power Conversion Equipment with low voltage battery input,, with Utility Interactive mode or Stand‑Alone mode with optional Auto‑Transformer Model T‑A. Wall mounted, permanently connected

Model(s)
ELS-5K, ELS-3K

 

Model

ELS-5K

ELS-3K

INPUT RATINGS (Battery to AC Grid Port)

 

Maximum input voltage

60Vdc

Range of input operating voltage

40-60Vdc

Maximum input current

110A

85A

Maximum input short circuit current (dc)

125A

97A

INPUT RATINGS (AC Grid to Battery Port and Backup Load)

 

Maximum input voltage

264Vac

Maximum input power

10000VA

Range of input operating voltage

211 - 264Vac

Range of full power input operating voltage

211 - 264Vac

Maximum input current

41.6A

30.6A

Frequency range

57-61Hz

OUTPUT RATINGS (Charge mode)

 

Charging output voltage operating range

40-60Vdc

Maximum continuous output current

110A

85A

Maximum output overcurrent protection

125A

97A

OUTPUT RATINGS (Standalone mode) 

 

Maximum continuous output power

5000VA

3680VA

Number of Phases

Split phase with neutral

Nominal output voltage

240Vac

Operating voltage range

211-264Vac(L-L)

105-132Vac(L-N)

Operating frequency range or single frequency

57-61Hz

Normal output frequency

60Hz

Maximum continuous output current

20.8A

15.3A

Maximum output overcurrent protection

26A

19.2A

Maximum output fault current (ac) and duration

60.66Apk, 10.5ms; 9.32Arms @3cycles; 7.23Arms@5cycles

OUTPUT RATINGS (Utility Interactive mode)

 

Maximum continuous output power

5000VA

3680VA

Nominal output voltage

240Vac

Operating voltage range (ac) (L-L)

211-264Vac

Number of Phases

Single phase without neutral

Normal output frequency

60 Hz

Operating frequency range or single frequency

58.8-61.2 Hz

Operating frequency range or single frequency (HECO)

57-63Hz

Output power factor rating

> 0.99 (+/- 0.8 adj.)

Maximum continuous output current

20.8A

15.3A

Maximum output overcurrent protection

26A

19.2A

Maximum output fault current (ac) and duration

60.66Apk, 10.5ms; 9.32Arms @3cycles; 7.23Arms@5cycles

Utility interconnection voltage and frequency trip limits and trip times

See note 1 and note 2

Trip limit and trip time accuracy

Voltage:

± 1%Vnom

Frequency:

± 0.01 Hz

Time:

1% but not less than 2 cycles(≈34ms)

Normal operation temperature range

-25˚C to 65˚C

Output power temperature derating and maximum full power operating ambient

See note 3

Storage temperature

-40˚C to 75˚C

Enclosure Rating Type

Type 4X

    

 

Auto-Transformer, model T-A, the electrical parameter and installation specification as following:

 

Model Name:

T-A

Rated output power

5000VA

10000VA

Max. apparent output power

7500 VA for 10sec

15000VA for 10sec

Rated grid voltage

120/240V Split Phase

Output Frequency

60HZ

Rated grid output current

41.67A

83.34A

Split Phase Imbalance (@Rated Power)

Up to 41.67A difference between phases

Up to 83.34A difference between phases

Dimensions (W*H*D)

524*315*186mm

Weight

30.5kg

41kg

Operating Temperature Range

-25 to +65 ºC

Ingress Protection

Type 4X

Installation

Wall mounted

 

 

Notes

 

  1. Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

 

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50Vnor

Rated

0.08

+/-80ms

B

0.75Vnor ≤ V< 0.995Vnor

Rated

0.16-600

+/-200ms

C

1.004Vnor< V < 1.125Vnor

Rated

0.16-600

+/-200ms

D

1.20Vnor ≤ V

Rated

0.08

+/-80ms

E

Rated

f > 60.5

60.1<f<62.0(adjustable)

0.16

+/-200ms

F

Rated

f < 59.3

57.0<f<59.9(adjustable)

0.16

+/-200ms

Reconnection time accuracy: 30-600S +/-10s

 

  1. While the Grid Support Utility interactive function evaluated according to IEEE 1547-2018, IEEE 1547a-2020 and IEEE 1547.1-2020, Utility Interconnection Voltage and Frequency Trip Limits and Trip Times setting as well as the enter service setting as following:

 

Shall trip

function

Abnormal Voltage Shall trip—Category III

Default settings

Ranges of allowable settings

Voltage

(p.u. of nominal voltage)

Clearing time

(s)

Voltage 

(p.u. of nominal voltage)

Clearing time

(s)

OV2

1.20

0.16

fixed at 1.20

fixed at 0.16

OV1

1.10

13.0

1.10 – 1.20

1.0 – 13.0

UV1

0.88

21.0

0.0 – 0.88

2.0 – 50.0

UV2

0.50

2.0

0.0 – 0.5

0.16 – 21.0

 

Shall trip

function

Abnormal Frequency Shall trip—Category III

Default settings

Ranges of allowable settings

Frequency

(Hz)

Clearing time

(s)

Frequency

(Hz)

Clearing time

(s)

OF2

62

0.16

61.8–66.0

0.16–1 000.0

OF1

61.2

300.0

61.0–66.0

180.0–1 000.0

UF1

58.5

300.0

50.0–59.0

180.0–1 000

UF2

56.5

0.16

50.0–57.0

0.16–1 000

 

Enter service criteria

Default settings

Ranges of allowable settings

Permit service

Enabled

Enabled/Disabled

Applicable voltage

within range

Minimum value

≥ 0.917 p.u.

0.88 p.u. to 0.95 p.u.

Maximum value

≤ 1.05 p.u.

1.05 p.u. to 1.06 p.u.

Frequency within

range

Minimum value

≥ 59.5 Hz

59.0 Hz to 59.9 Hz

Maximum value

≤ 60.1 Hz

60.1 Hz to 61.0 Hz

Time accuracy: 1% but not less than 2 cycles(34ms)

 

  1. Operating power envelope as a function of ambient temperature: ELS-5K

 

  1. Battery DC Input, Rated AC output

 

-25°C

25°C

45°C

65°C

60Vdc

5000W

5000W

5000W

3000W

52Vdc

5000W

5000W

5000W

3000W

 

  1. All models meet the surge requirements of IEEE C62.41.2-2002, Location Category B (6kV).  Tests were performed using ring wave and combination waveforms, both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.

 

  1. Utility interactive evaluations were conducted with firmware flashed into a single IC, checksum was indicated by following:

Model

Microprocessor/FPGA

Firmware

Checksum

Remark

ELS-5K

ELS-3K

HPC03P02(IXC2)

V1.0.13

61935332796BF6F202E4967B0ED7A475

UL1741SA

V1.2.3.2 

FCC76F9F9FA03623D466F825002AFB1E

UL1741SB

 

  1. This product's software has not been evaluated to the requirements of UL 1998.

 

  1. For Power Conversion Equipment, models ELS-5K and ELS-3K, the stand-alone mode can optionally operate with an external auto-transformer T-A.

 

  1. Models ELS-5K and ELS-3K were evaluated to meet the California Rule 21 grid support functions according to UL 1741 Supplement SA8-SA18.

 

  1. Grid Support Utility Interactive Inverter, Models ELS-5K and ELS-3K were evaluated with reactive power priority in UL1741 SA13 Volt/Var Mode (Q(V)) Test.  

 

  1. Models ELS-5K and ELS-3K are verified according to UL 1741 Supplement SB and IEEE 1547.1-2020 with the SRDs of IEEE 1547-2018, IEEE 1547a-2020 and Hawaiian Electric Co. SRD-V2.0. While the grid support function evaluated according to IEEE 1547.1-2020, the interoperability is verified with IEEE 2030.5-2018 communication protocol.
   
  
  
  
   
   
  
  
  
  
   
  
  
   
  
   
   
  
   
  
  
  
  
  
   
   
  
  
   
  
  
  
  
  
  
   
   
  
  
   
  
  
  
  
  
  
  

 

 

Auto‑Transformer, the electrical parameter and installation specification

Model(s)
T-A

Models rating as follow:

Model Name:

T-A

Rated output power

5000VA

Max. apparent output power

7500 VA for 10sec

Rated grid voltage

120/240V Split Phase

Output Frequency

60HZ

Rated grid output current

41.67A

Split Phase Imbalance (@Rated Power)

Up to 41.67A di?erence between phases

Dimensions (W*H*D)

627*362*167mm

Weight

33kg

Operating Temperature Range

-25 to +65 ºC

Ingress Protection

Type 4X

Installation

Wall mounted

Notes:

  1. Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50Vnor

Rated

0.08

+/-80ms

B

0.75Vnor ¡Ü V< 0.995Vnor

Rated

0.16-600

+/-200ms

C

1.004Vnor< V < 1.125Vnor

Rated

0.16-600

+/-200ms

D

1.20Vnor ¡Ü V

Rated

0.08

+/-80ms

E

Rated

f > 60.5

60.1<f<62.0(adjustable)

0.16

+/-200ms

F

Rated

f < 59.3

57.0<f<59.9(adjustable)

0.16

+/-200ms

Reconnection time accuracy: 30-600S +/-10s

 

  1. Operating power envelope as a function of ambient temperature: ELS-5K

1)    Battery DC Input, Rated AC output

 

-25¡ãC

25¡ãC

45¡ãC

65¡ãC

60Vdc

5000W

5000W

5000W

3000W

52Vdc

5000W

5000W

5000W

3000W

  1. All models meet the surge requirements of IEEE C62.41.2-2002, Location Category B (6kV). Tests were performed using ring wave and combination waveforms, both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.

 

  1. Utility interactive evaluations were conducted with firmware flashed into a single IC, checksum was indicated by following:

 

Model

Microprocessor/FPGA

Firmware

Checksum

ELS-5K

ELS-3K

 

V1.0.13

 

  1. This product's software has not been evaluated to the requirements of UL 1998.
  2. For Power Conversion Equipment, models ELS-5K and ELS-3K, the stand-alone mode can optionally operate with an external auto-transformer T-A.

Photovoltaic Rapid Shutdown System Equipment, used to cut off the DC connection of PV modules after the Transmitter power supply circuit breaker is off. Rack mounted or mounted to the PV module with adhesive. PLC communication used.

Model(s)
RSD-S-PLC-B, RSD-S-PLC-A

Models rating as follow:

Rating type

RSD-S-PLC-B

RSD-S-PLC-A

a) Maximum System Voltage

1500V

1000V

b) Range of input operating voltage (dc)

8V-80V

8V-80V

c) Max input current (ac or dc)

15A

15A

d) Max Input short circuit current

15A

15A

e) Rapid shutdown time limit

Less than 15s

Less than 15s

f) Normal operation temperature range

-40¡ãC - 85¡ãC

-40¡ãC - 85¡ãC

g) type of PVRSS or PVRSE (RS1 or RS2)

RS2

RS2

h) Enclosure Type

Type 6P (conform to test requirement)

Model(s)
Transmitter-PLC

Models rating as follow:

Rating type

RSD-S-PLC-B

RSD-S-PLC-A

a) Maximum System Voltage

1500V

1000V

b) Range of input operating voltage (dc)

8V-80V

8V-80V

c) Max input current (ac or dc)

15A

15A

d) Max Input short circuit current

15A

15A

e) Rapid shutdown time limit

Less than 15s

Less than 15s

f) Normal operation temperature range

-40¡ãC - 85¡ãC

-40¡ãC - 85¡ãC

g) type of PVRSS or PVRSE (RS1 or RS2)

RS2

RS2

h) Enclosure Type

Type 6P (conform to test requirement)

Rating type

Transmitter-PLC/

Transmitter-PLC-PCBA

Transmitter-PLC-1P

a) Maximum System Voltage

/

/

b) Range of input operating voltage (dc)

12V or 24V

12V or 24V

c) Max input current (ac or dc)

0.8A

0.5A

d) Max Input short circuit current

/

/

e) Rapid shutdown time limit

/

/

f) Normal operation temperature range

-40¡ãC - 100¡ãC

-40¡ãC - 100¡ãC

g) type of PVRSS or PVRSE (RS1 or RS2)

/

/

h) Enclosure Type

See note 1

See note 1

 

Note:

  1. The transmitter-PLC shall be mounted in enclosure conforming to application environment conforming to relevant standard.
  2. Photovoltaic Rapid Shutdown Function has also been evaluated according to NEC-2017 and NEC-2020 Section 690.12 applicable requirement.

 

APsmart Rapid shutdownSystem:

Model

Attenuators

Initiation Device

System Ratings

Type-A

RSD-S-PLC-A

Transmitter-PLC

System voltage 1000Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

Type-B

RSD-S-PLC-B

Transmitter-PLC

System voltage 1500Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

Type-C

RSD-S-PLC-A

Transmitter-PLC-PCBA

System voltage 1000Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

Type-D

RSD-S-PLC-B

Transmitter-PLC-PCBA

System voltage 1500Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

 

Model

Attenuators

Initiation Device

Inverter

System Ratings

APsmart’s RSD system, PVRSS: Sunspec

Altenergy Power System Inc.

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500

 

Zhejiang Twinsel Electronic Technology Co., Ltd.

PV-SY020-A

PV-SY020

 

Baoding Yitong PV Science&Technology Co., Ltd.

YT-RSD-P-1000

YT-RSD-P-1500

Altenergy Power System Inc.

Transmitter-PLC

Transmitter-PLC-PCBA

Transmitter-PLC-1P

 

Zhejiang Twinsel Electronic Technology Co., Ltd.

PV-SY020-PLC

PV-SY020-PCBA

 

Baoding Yitong PV Science&Technology Co., Ltd.

Transmitter-PLC

Transmitter-PLC-PCBA

SHANGHAI CHINT POWER SYSTEMS CO., LTD.:

CPS SCA60KTL-DO/US-480

CPS SCA50KTL-DO/US-480

CPS SCA36KTL-DO/US-480

CPS SCA25KTL-DO-R/US-480

CPS SCA20KTL-DO-R/US-480

CPS SCA25KTL-DO/US-208

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

Delta Electronics (Shanghai) Co., Ltd.

M10-4-TL-US

M10-TL-US

M8-TL-US

M6-TL-US

M5-TL-US

M4-TL-US

E8-TL-US

E6-TL-US

E4-TL-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

LG ELECTRONICS, INC.

D007KEEN261

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

Solectria Renewables, LLC

PVI 50TL-480

PVI 60TL-480

PVI 20TL-480-R

PVI 25TL-480-R

PVI 25TL-208

PVI-36TL-480-V2

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

JIANGSU GOODWE POWER SUPPLY TECHNOLOGY CO., LTD.

GW9600A-ES?GW8600A-ES, GW7600A-ES,

GW7000A-ES, GW6000A-ES, GW5000A-ES,

GW9600A-MS, GW8600A-MS, GW7600A-MS, GW7000A-MS, GW6000A-MS, GW5000A-MS,

GW9600A-IS, GW8600A-IS, GW7600A-IS, GW7000A-IS,

GW6000A-IS, GW5000A-IS

GW9600H-ES, GW8600H-ES, GW7600H-ES, GW7000H-ES,

GW6000H-ES, GW5000H-ES,

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the DC Switch on the inverter.

Shenzhen Growatt New Energy

Technology Co., Ltd

SPH 3000TL BL-US,

SPH 3600TL BL-US,

SPH 4000TL BL-US,

SPH 4600TL BL-US,

SPH 5000TL BL-US,

SPH 6000TL BL-US

550 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

Shenzhen Growatt New Energy

Technology Co., Ltd

MIN 8200TL-XH-US,

MIN 9000TL-XH-US, MIN 10000TL-XH-US,

MIN 11400TL-XH-US,

MIN 3000TL-XH-US,

MIN 3800TL-XH-US, MIN 5000TL-XH-US, MIN 6000TL-XH-US, MIN 7600TL-XH-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

FIMER S.p.A.:

1)UNO-DM-3.3-TL-PLUS-US-XYZ-ABC-DE-F,

2) UNO-DM-3.8-TL-PLUS-US-XYZ-ABC-DE-F,

3) UNO-DM-4.6-TL-PLUS-US-XYZ-ABC-DE-F,

4) UNO-DM-5.0-TL-PLUS-US-XYZ-ABC-DE-F.

(X: blank, S;

Y = blank, B, E, Z;

Z = blank, M;

A = blank, X;

B = blank, R;

C = blank, A;

D = blank, Q;

E = blank, U;

F = blank, AP, TI)

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

FIMER S.p.A.:

UNO-DM-6.0-TL-PLUS-US-XYZ-ABC-DE-F

(X: blank, S;

Y = blank, B, E, Z; Z = blank, M;

A = blank, X;

B = blank, R;

C = blank, A;

D = blank, Q;

E = blank, U;

F = blank, AP, TI)

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power

 

Delta Electronics, Inc.

E10_BDI

E8_BDI

E6_BDI

E4_BDI

E10-TL-US

E8 Plus-TL-US

EC8-US

EC6-US

EC4-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power

Shenzhen Eternalplanet Energy Pingshan Ltd.:

HNA7W,

HNA7W_TT, HNA7W_AT,

HNA7G,

HNA7G_TT,

HNA7G_AT

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

Afore New Energy Technology (Shanghai) Co., Ltd.:

AF9.6K-DH

AF8.6K-DH

AF8K-DH

AF7.6K-DH

AF7K-DH

AF6K-DH

AF5.5K-DH

AF5K-DH

AF4.6K-DH

AF4K-DH

AF3.6K-DH

AF3K-DH

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

FOXESS CO., LTD.:

H1-3.8-US,

H1-5.7-US,

H1-7.6-US,

H1-9.6-US,

H1-11.4-US.

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

APsmart’s RSD system, PVRSS: Sunspec

Altenergy Power System Inc.

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-15-1500

RSD-D-20-1500

 

Zhejiang Twinsel Electronic Technology Co., Ltd.

PV-SY020-A

PV-SY020

 

Baoding Yitong PV Science&Technology Co., Ltd.

YT-RSD-P-1000

YT-RSD-P-1500

Altenergy Power System Inc.

Transmitter-PLC

Transmitter-PLC-PCBA

Transmitter-PLC-1P

 

Zhejiang Twinsel Electronic Technology Co., Ltd.

PV-SY020-PLC

PV-SY020-PCBA

 

Baoding Yitong PV Science&Technology Co., Ltd.

Transmitter-PLC

Transmitter-PLC-PCBA

Ginlong Technologies Co., Ltd.

Solis-75K-5G-US,

Solis-80K-5G-US,

Solis-90K-5G-US,

Solis-100K-5G-US,

S5-GC75K-US,

S5-GC80K-US,

S5-GC90K-US,

S5-GC100K-US.

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of inverter power of AC Grid.

CSI Solar Co., Ltd.

CSI-75K-T480GL02-U,

CSI-80K-T480GL02-U,

CSI-90K-T480GL02-U,

CSI-100K-T480GL02-U.

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of inverter power of AC Grid.

APsmart’s RSD system, PVRSS: Sunspec

Altenergy Power System Inc.:

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500.

Altenergy Power System Inc.:

Transmitter-PLC,

Transmitter-PLC-1P

Jiangsu RCT Power Energy Technology Co., Ltd:

Power Storage DC US-8.0

520 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the disconnecting external AC breaker in the field.

 

Model

Attenuators

Initiation Device

Inverter

System Ratings

APsmart Rapid shutdown System, PVRSS: Sunspec

Altenergy Power System Inc.

RSD-S-PLC-A;

RSD-S-PLC-B;

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500



Zhejiang Twinsel Electronic Technology Co., Ltd.
PV-SY020-A; PV-SY020;

Baoding Yitong PV Science & Technology Co., Ltd.

YT-RSD-P-1000; YT-RSD-P-1500;

Altenergy Power System Inc.

Transmitter-PLC

Manufacturer: SolaX Power Network Technology (Zhe jiang) Co., Ltd.

Family series (1) Models: A1-Hybrid-6.0-US, A1-Hybrid-7.0-US, A1-Hybrid-7.6-US, A1-Hybrid-8.6-US;

Family series (2) Models: A1-6.0-US, A1-7.0-US, A1-7.6-US, A1-8.6-US

600 Vdc maximum system voltage. Rapid shutdown time limit 30 s with inverter.

Family series (1) Initiated by external emergency button with signal wire connected to the Inverter¡¯s ELV circuit.

Family series (2) Initiated by the loss of AC Grid.

Manufacturer: Hanwha Q CELLS America Inc.

Family series (1):

Q. HOME+ HYB-G1-X.X series, models:

Q.HOME+ HYB-G1-6.0, Q.HOME+ HYB-G1-7.0, Q.HOME+ HYB-G1-7.6, Q.HOME+ HYB-G1-8.6;

Family series (2):

Q.HOME+ AC-G1-X.X series, models:

Q.HOME+ AC-G1-6.0, Q.HOME+ AC-G1-7.0, Q.HOME+ AC-G1-7.6, Q.HOME+ AC-G1-8.6;

600 Vdc maximum system voltage. Rapid shutdown time limit 30 s with inverter.

Family series (1) Initiated by external emergency button with signal wire connected to the Inverter¡¯s ELV circuit.

Family series (2) Initiated by the loss of AC Grid.

To the requirements of
CSA C22.2 NO. 330:23, UL 1741 (Third Edition)

Model(s)
Transmitter-PLC-PCBA, Transmitter-PLC-1P

Models rating as follow:

Rating type

RSD-S-PLC-B

RSD-S-PLC-A

a) Maximum System Voltage

1500V

1000V

b) Range of input operating voltage (dc)

8V-80V

8V-80V

c) Max input current (ac or dc)

15A

15A

d) Max Input short circuit current

15A

15A

e) Rapid shutdown time limit

Less than 15s

Less than 15s

f) Normal operation temperature range

-40¡ãC - 85¡ãC

-40¡ãC - 85¡ãC

g) type of PVRSS or PVRSE (RS1 or RS2)

RS2

RS2

h) Enclosure Type

Type 6P (conform to test requirement)

Rating type

Transmitter-PLC/

Transmitter-PLC-PCBA

Transmitter-PLC-1P

a) Maximum System Voltage

/

/

b) Range of input operating voltage (dc)

12V or 24V

12V or 24V

c) Max input current (ac or dc)

0.8A

0.5A

d) Max Input short circuit current

/

/

e) Rapid shutdown time limit

/

/

f) Normal operation temperature range

-40¡ãC - 100¡ãC

-40¡ãC - 100¡ãC

g) type of PVRSS or PVRSE (RS1 or RS2)

/

/

h) Enclosure Type

See note 1

See note 1

 

Note:

  1. The transmitter-PLC shall be mounted in enclosure conforming to application environment conforming to relevant standard.
  2. Photovoltaic Rapid Shutdown Function has also been evaluated according to NEC-2017 and NEC-2020 Section 690.12 applicable requirement.

 

APsmart Rapid shutdownSystem:

Model

Attenuators

Initiation Device

System Ratings

Type-A

RSD-S-PLC-A

Transmitter-PLC

System voltage 1000Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

Type-B

RSD-S-PLC-B

Transmitter-PLC

System voltage 1500Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

Type-C

RSD-S-PLC-A

Transmitter-PLC-PCBA

System voltage 1000Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

Type-D

RSD-S-PLC-B

Transmitter-PLC-PCBA

System voltage 1500Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

 

Model

Attenuators

Initiation Device

Inverter

System Ratings

APsmart’s RSD system, PVRSS: Sunspec

Altenergy Power System Inc.

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500

 

Zhejiang Twinsel Electronic Technology Co., Ltd.

PV-SY020-A

PV-SY020

 

Baoding Yitong PV Science&Technology Co., Ltd.

YT-RSD-P-1000

YT-RSD-P-1500

Altenergy Power System Inc.

Transmitter-PLC

Transmitter-PLC-PCBA

Transmitter-PLC-1P

 

Zhejiang Twinsel Electronic Technology Co., Ltd.

PV-SY020-PLC

PV-SY020-PCBA

 

Baoding Yitong PV Science&Technology Co., Ltd.

Transmitter-PLC

Transmitter-PLC-PCBA

SHANGHAI CHINT POWER SYSTEMS CO., LTD.:

CPS SCA60KTL-DO/US-480

CPS SCA50KTL-DO/US-480

CPS SCA36KTL-DO/US-480

CPS SCA25KTL-DO-R/US-480

CPS SCA20KTL-DO-R/US-480

CPS SCA25KTL-DO/US-208

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

Delta Electronics (Shanghai) Co., Ltd.

M10-4-TL-US

M10-TL-US

M8-TL-US

M6-TL-US

M5-TL-US

M4-TL-US

E8-TL-US

E6-TL-US

E4-TL-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

LG ELECTRONICS, INC.

D007KEEN261

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

Solectria Renewables, LLC

PVI 50TL-480

PVI 60TL-480

PVI 20TL-480-R

PVI 25TL-480-R

PVI 25TL-208

PVI-36TL-480-V2

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

JIANGSU GOODWE POWER SUPPLY TECHNOLOGY CO., LTD.

GW9600A-ES?GW8600A-ES, GW7600A-ES,

GW7000A-ES, GW6000A-ES, GW5000A-ES,

GW9600A-MS, GW8600A-MS, GW7600A-MS, GW7000A-MS, GW6000A-MS, GW5000A-MS,

GW9600A-IS, GW8600A-IS, GW7600A-IS, GW7000A-IS,

GW6000A-IS, GW5000A-IS

GW9600H-ES, GW8600H-ES, GW7600H-ES, GW7000H-ES,

GW6000H-ES, GW5000H-ES,

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the DC Switch on the inverter.

Shenzhen Growatt New Energy

Technology Co., Ltd

SPH 3000TL BL-US,

SPH 3600TL BL-US,

SPH 4000TL BL-US,

SPH 4600TL BL-US,

SPH 5000TL BL-US,

SPH 6000TL BL-US

550 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

Shenzhen Growatt New Energy

Technology Co., Ltd

MIN 8200TL-XH-US,

MIN 9000TL-XH-US, MIN 10000TL-XH-US,

MIN 11400TL-XH-US,

MIN 3000TL-XH-US,

MIN 3800TL-XH-US, MIN 5000TL-XH-US, MIN 6000TL-XH-US, MIN 7600TL-XH-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

FIMER S.p.A.:

1)UNO-DM-3.3-TL-PLUS-US-XYZ-ABC-DE-F,

2) UNO-DM-3.8-TL-PLUS-US-XYZ-ABC-DE-F,

3) UNO-DM-4.6-TL-PLUS-US-XYZ-ABC-DE-F,

4) UNO-DM-5.0-TL-PLUS-US-XYZ-ABC-DE-F.

(X: blank, S;

Y = blank, B, E, Z;

Z = blank, M;

A = blank, X;

B = blank, R;

C = blank, A;

D = blank, Q;

E = blank, U;

F = blank, AP, TI)

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

FIMER S.p.A.:

UNO-DM-6.0-TL-PLUS-US-XYZ-ABC-DE-F

(X: blank, S;

Y = blank, B, E, Z; Z = blank, M;

A = blank, X;

B = blank, R;

C = blank, A;

D = blank, Q;

E = blank, U;

F = blank, AP, TI)

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power

 

Delta Electronics, Inc.

E10_BDI

E8_BDI

E6_BDI

E4_BDI

E10-TL-US

E8 Plus-TL-US

EC8-US

EC6-US

EC4-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power

Shenzhen Eternalplanet Energy Pingshan Ltd.:

HNA7W,

HNA7W_TT, HNA7W_AT,

HNA7G,

HNA7G_TT,

HNA7G_AT

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

Afore New Energy Technology (Shanghai) Co., Ltd.:

AF9.6K-DH

AF8.6K-DH

AF8K-DH

AF7.6K-DH

AF7K-DH

AF6K-DH

AF5.5K-DH

AF5K-DH

AF4.6K-DH

AF4K-DH

AF3.6K-DH

AF3K-DH

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

FOXESS CO., LTD.:

H1-3.8-US,

H1-5.7-US,

H1-7.6-US,

H1-9.6-US,

H1-11.4-US.

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

APsmart’s RSD system, PVRSS: Sunspec

Altenergy Power System Inc.

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-15-1500

RSD-D-20-1500

 

Zhejiang Twinsel Electronic Technology Co., Ltd.

PV-SY020-A

PV-SY020

 

Baoding Yitong PV Science&Technology Co., Ltd.

YT-RSD-P-1000

YT-RSD-P-1500

Altenergy Power System Inc.

Transmitter-PLC

Transmitter-PLC-PCBA

Transmitter-PLC-1P

 

Zhejiang Twinsel Electronic Technology Co., Ltd.

PV-SY020-PLC

PV-SY020-PCBA

 

Baoding Yitong PV Science&Technology Co., Ltd.

Transmitter-PLC

Transmitter-PLC-PCBA

Ginlong Technologies Co., Ltd.

Solis-75K-5G-US,

Solis-80K-5G-US,

Solis-90K-5G-US,

Solis-100K-5G-US,

S5-GC75K-US,

S5-GC80K-US,

S5-GC90K-US,

S5-GC100K-US.

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of inverter power of AC Grid.

CSI Solar Co., Ltd.

CSI-75K-T480GL02-U,

CSI-80K-T480GL02-U,

CSI-90K-T480GL02-U,

CSI-100K-T480GL02-U.

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of inverter power of AC Grid.

APsmart’s RSD system, PVRSS: Sunspec

Altenergy Power System Inc.:

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500.

Altenergy Power System Inc.:

Transmitter-PLC,

Transmitter-PLC-1P

Jiangsu RCT Power Energy Technology Co., Ltd:

Power Storage DC US-8.0

520 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the disconnecting external AC breaker in the field.

 

Model

Attenuators

Initiation Device

Inverter

System Ratings

APsmart Rapid shutdown System, PVRSS: Sunspec

Altenergy Power System Inc.

RSD-S-PLC-A;

RSD-S-PLC-B;

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500



Zhejiang Twinsel Electronic Technology Co., Ltd.
PV-SY020-A; PV-SY020;

Baoding Yitong PV Science & Technology Co., Ltd.

YT-RSD-P-1000; YT-RSD-P-1500;

Altenergy Power System Inc.

Transmitter-PLC

Manufacturer: SolaX Power Network Technology (Zhe jiang) Co., Ltd.

Family series (1) Models: A1-Hybrid-6.0-US, A1-Hybrid-7.0-US, A1-Hybrid-7.6-US, A1-Hybrid-8.6-US;

Family series (2) Models: A1-6.0-US, A1-7.0-US, A1-7.6-US, A1-8.6-US

600 Vdc maximum system voltage. Rapid shutdown time limit 30 s with inverter.

Family series (1) Initiated by external emergency button with signal wire connected to the Inverter¡¯s ELV circuit.

Family series (2) Initiated by the loss of AC Grid.

Manufacturer: Hanwha Q CELLS America Inc.

Family series (1):

Q. HOME+ HYB-G1-X.X series, models:

Q.HOME+ HYB-G1-6.0, Q.HOME+ HYB-G1-7.0, Q.HOME+ HYB-G1-7.6, Q.HOME+ HYB-G1-8.6;

Family series (2):

Q.HOME+ AC-G1-X.X series, models:

Q.HOME+ AC-G1-6.0, Q.HOME+ AC-G1-7.0, Q.HOME+ AC-G1-7.6, Q.HOME+ AC-G1-8.6;

600 Vdc maximum system voltage. Rapid shutdown time limit 30 s with inverter.

Family series (1) Initiated by external emergency button with signal wire connected to the Inverter¡¯s ELV circuit.

Family series (2) Initiated by the loss of AC Grid.

To the requirements of
UL 1741 (Second Edition; Reprint with Revisions Through and Including

APsmart Rapid Shutdown System:

Model(s)Electric Rating
APsmart Rapid Shutdown System:Refer table

APsmart Rapid Shutdown System:

Model

Attenuators

Initiation Device

System Ratings

Type-A

RSD-S-PLC-A

Transmitter-PLC

System voltage 1000Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

Type-B

RSD-S-PLC-B

Transmitter-PLC

System voltage 1500Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

 

 

Type-C

RSD-S-PLC-A

Transmitter-PLC-PCBA

System voltage 1000Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

Type-D

RSD-S-PLC-B

Transmitter-PLC-PCBA

System voltage 1500Vdc, Attenuators Input:

8~80Vdc, 15Amax per module, 15A max input short circuit. Attenuators Output: 8~80Vdc, 15Amax, 800W max per module.

Rapid shutdown time limit 15s.

Initiated by the loss of AC power

 

 

Model

Attenuators

Initiation Device

Inverter

System Ratings

APsmart’s RSD system, PVRSS: Sunspec

ALTENERGY POWER SYSTEM INC.

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500

 

 

ALTENERGY POWER SYSTEM INC.

Transmitter-PLC

Transmitter-PLC-PCBA

Transmitter-PLC-1P

 

Shanghai CHINT Power Systems Co., Ltd.

CPS SCA60KTL-DO/US-480

CPS SCA50KTL-DO/US-480

CPS SCA36KTL-DO/US-480

CPS SCA25KTL-DO-R/US-480

CPS SCA20KTL-DO-R/US-480

CPS SCA25KTL-DO/US-208

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

Shanghai CHINT Power Systems Co., Ltd.

Family series:

CPS ECH12KTL/US, CPS ECH11.4KTL/US CPS ECH9.6KTL/US, CPS ECH7.6KTL/US, CPS ECH6KTL/US, CPS ECH5KTL/US, CPS ECH3.8KTL/US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30 s with inverter.

 

Family series Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

Delta Electronics (Shanghai) Co., Ltd.

M10-4-TL-US

M10-TL-US

M8-TL-US

M6-TL-US

M5-TL-US

M4-TL-US

E8-TL-US

E6-TL-US

E4-TL-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

LG ELECTRONICS, INC.

D007KEEN261

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

Solectria Renewables, LLC

PVI 50TL-480

PVI 60TL-480

PVI 20TL-480-R

PVI 25TL-480-R

PVI 25TL-208

PVI-36TL-480-V2

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

JIANGSU GOODWE POWER SUPPLY TECHNOLOGY CO., LTD.

GW9600A-ESGW8600A-ES, GW7600A-ES,

GW7000A-ES, GW6000A-ES, GW5000A-ES,

GW9600A-MS, GW8600A-MS, GW7600A-MS, GW7000A-MS, GW6000A-MS, GW5000A-MS,

GW9600A-IS, GW8600A-IS, GW7600A-IS, GW7000A-IS,

GW6000A-IS, GW5000A-IS

GW9600H-ES, GW8600H-ES, GW7600H-ES, GW7000H-ES,

GW6000H-ES, GW5000H-ES,

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the DC Switch on the inverter.

Shenzhen Growatt New Energy

Technology Co., Ltd

SPH 3000TL BL-US,

SPH 3600TL BL-US,

SPH 4000TL BL-US,

SPH 4600TL BL-US,

SPH 5000TL BL-US,

SPH 6000TL BL-US

550 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

Shenzhen Growatt New Energy

Technology Co., Ltd

MIN 8200TL-XH-US,

MIN 9000TL-XH-US, MIN 10000TL-XH-US,

MIN 11400TL-XH-US,

MIN 3000TL-XH-US,

MIN 3800TL-XH-US, MIN 5000TL-XH-US, MIN 6000TL-XH-US, MIN 7600TL-XH-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

FIMER S.p.A.:

1)UNO-DM-3.3-TL-PLUS-US-XYZ-ABC-DE-F,

2) UNO-DM-3.8-TL-PLUS-US-XYZ-ABC-DE-F,

3) UNO-DM-4.6-TL-PLUS-US-XYZ-ABC-DE-F,

4) UNO-DM-5.0-TL-PLUS-US-XYZ-ABC-DE-F.

(X: blank, S;

Y = blank, B, E, Z;

Z = blank, M;

A = blank, X;

B = blank, R;

C = blank, A;

D = blank, Q;

E = blank, U;

F = blank, AP, TI)

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power.

FIMER S.p.A.:

UNO-DM-6.0-TL-PLUS-US-XYZ-ABC-DE-F

(X: blank, S;

Y = blank, B, E, Z; Z = blank, M;

A = blank, X;

B = blank, R;

C = blank, A;

D = blank, Q;

E = blank, U;

F = blank, AP, TI)

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power

 

Delta Electronics, Inc.

E10_BDI

E8_BDI

E6_BDI

E4_BDI

E10-TL-US

E8 Plus-TL-US

EC8-US

EC6-US

EC4-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power

Shenzhen Eternalplanet Energy Pingshan Ltd.:

HNA7W,

HNA7W_TT, HNA7W_AT,

HNA7G,

HNA7G_TT,

HNA7G_AT

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

Afore New Energy Technology (Shanghai) Co., Ltd.:

AF9.6K-DH

AF8.6K-DH

AF8K-DH

AF7.6K-DH

AF7K-DH

AF6K-DH

AF5.5K-DH

AF5K-DH

AF4.6K-DH

AF4K-DH

AF3.6K-DH

AF3K-DH

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

FOXESS CO., LTD.:

H1-3.8-US,

H1-5.7-US,

H1-7.6-US,

H1-9.6-US,

H1-11.4-US.

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

8 Star Energy North America Inc:

Force 3.8DC

Force 5.7DC

Force 7.6DC

Force 9.6DC

Force 11.4DC

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

Schneider Electric IT Corporation.

 

Model: HY8K1NA1

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30 s with inverter.

 

Inverter Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

APsmart’s RSD system, PVRSS: Sunspec

ALTENERGY POWER SYSTEM INC.

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-15-1500

RSD-D-20-1500

 

 

ALTENERGY POWER SYSTEM INC.

Transmitter-PLC

Transmitter-PLC-PCBA

Transmitter-PLC-1P

 

Ginlong Technologies Co., Ltd.

Solis-75K-5G-US,

Solis-80K-5G-US,

Solis-90K-5G-US,

Solis-100K-5G-US,

S5-GC75K-US,

S5-GC80K-US,

S5-GC90K-US,

S5-GC100K-US.

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of inverter power of AC Grid.

CSI Solar Co., Ltd.

CSI-75K-T480GL02-U,

CSI-80K-T480GL02-U,

CSI-90K-T480GL02-U,

CSI-100K-T480GL02-U.

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of inverter power of AC Grid.

APsmart’s RSD system, PVRSS: Sunspec

ALTENERGY POWER SYSTEM INC.:

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500.

ALTENERGY POWER SYSTEM INC.:

Transmitter-PLC,

Transmitter-PLC-1P

Jiangsu RCT Power Energy Technology Co., Ltd:

Power Storage DC US-8.0

520 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the disconnecting external AC breaker in the field.

 

Model

Attenuators

Initiation Device

Inverter

System Ratings

APsmart’s RSD system, PVRSS: Sunspec

ALTENERGY POWER SYSTEM INC.

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500

 

Integrated in Fronius inverter as listed in the just right column of this table

Fronius International GmbH

Fronius Symo Advanced 10.0-3 208-240

Fronius Symo Advanced 12.0-3 208-240

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power

Fronius International GmbH

Fronius Symo Advanced 15.0-3 480

Fronius Symo Advanced 20.0-3 480

Fronius Symo Advanced 22.7-3 480

Fronius Symo Advanced 24.0-3 480

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter

 

Initiated by the loss of AC power

Fronius International GmbH

Primo GEN24 3.8 208-240

Primo GEN24 5.0 208-240

Primo GEN24 6.0 208-240

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by external buttons with signal wire connected to the WSD interface of the Inverter.

Integrated in Ginlong inverters as listed in the just right column of this table

Ginlong Technologies Co., Ltd.

Solis-50K-US-SW;

Solis-50K-US-LSW;

Solis-66K-US-F-SW; Solis-66K-US-F-LSW; 

Solis-60K-US-F-SW; Solis-60K-US-F-LSW;

Solis-50K-US-F-SW; Solis-50K-US-F-LSW; 

Solis-40K-US-F-SW; Solis-40K-US-LSW; 

Solis-40K-US-SW;

Solis-36K-US-SW;

Solis-36K-US-F-SW; Solis-36K-US-LSW; 

Solis-30K-US-F-SW; Solis-30K-US-LSW; 

Solis-30K-US-SW;

Solis-25K-US-SW;

Solis-25K-US-F-SW; Solis-25K-US-LSW;

1000 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power

Integrated in Ginlong inverters as listed in the just right column of this table

Ginlong Technologies Co., Ltd.

Solis-1P10K-4G-US; Solis-1P9K-4G-US;

Solis-1P8.6K-4G-US; Solis-1P8K-4G-US;

Solis-1P7.6K-4G-US; Solis-1P7K-4G-US;

Solis-1P6K-4G-US; Solis-1P6K2-4G-US;

Solis-1P5K-4G-US; Solis-1P4.6K-4G-US;

Solis-1P4K-4G-US; Solis-1P3.6K-4G-US;

Solis-1P3K-4G-US; Solis-1P2.5K-4G-US;

Solis-1P2K-4G-US; Solis-1P1.5K-4G-US;

Solis-1P1K-4G-US;

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of inverter power of AC Grid.

Integrated in Ginlong inverters as listed in the just right column of this table

Ginlong Technologies Co., Ltd.

RHI-1P5K-HVES-5G; 

RHI-1P6K-HVES-5G;

RHI-1P7K-HVES-5G; 

RHI-1P7.6K-HVES-5G; 

RHI-1P8K-HVES-5G;

RHI-1P9K-HVES-5G; 

RHI-1P10K-HVES-5G;

500 Vdc maximum

system voltage.

 

Rapid shutdown time

limit 30s with inverter.

 

Initiated by the loss of AC power

Integrated in Candian Solar inverters as listed in the just right column of this table

Canadian Solar Inc. :

CSI-66K-T480GL01-UB, 

CSI-60K-T480GL01-UB,

CSI-50K-T480GL01-UB, 

CSI-40K-T480GL01-UB,

CSI-36K-T480GL01-UB,

CSI-30K-T480GL01-UB, 

CSI-25K-T480GL01-UB.

CSI-25KTL-GS-FLB,

CSI-30KTL-GS-FLB,

CSI-36KTL-GS-FLB,

CSI-40KTL-GS-FLB,

CSI-40KTL-GS-B,

CSI-50KTL-GS-FLB,

CSI-50KTL-GS-B,

CSI-60KTL-GS-B,

CSI-66KTL-GS-B

1000 Vdc maximum

system voltage.

 

Rapid shutdown time limit 30s with inverter.

 

Initiated by the loss of AC power

 

Model

Attenuators

Initiation Device

Inverter

System Ratings

APsmart Rapid Shutdown System, PVRSS: Sunspec

ALTENERGY POWER SYSTEM INC.

RSD-S-PLC-A

RSD-S-PLC-B

RSD-D-15-1000

RSD-D-20-1000

RSD-D-25-1000

RSD-D-15-1500

RSD-D-20-1500

RSD-D-25-1500



 

ALTENERGY POWER SYSTEM INC.

Transmitter-PLC

Manufacturer: SolaX Power Network Technology (Zhejiang) Co., Ltd.

Family series (1) Models: A1-Hybrid-6.0-US, A1-Hybrid-7.0-US, A1-Hybrid-7.6-US, A1-Hybrid-8.6-US;

Family series (2)
Models: A1-6.0-US, A1-7.0-US, A1-7.6-US, A1-8.6-US

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30 s with inverter.

 

Family series (1) Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

 

Family series (2) Initiated by the loss of AC Grid.

Manufacturer: Hanhua Q CELLS America Inc.

Family series (1):

Q. HOME+ HYB-G1-X.X series, models:

Q.HOME+ HYB-G1-6.0, Q.HOME+ HYB-G1-7.0, Q.HOME+ HYB-G1-7.6, Q.HOME+ HYB-G1-8.6;

 

Family series (2):

Q.HOME+ AC-G1-X.X series, models:

Q.HOME+ AC-G1-6.0, Q.HOME+ AC-G1-7.0, Q.HOME+ AC-G1-7.6, Q.HOME+ AC-G1-8.6;

600 Vdc maximum system voltage.

 

Rapid shutdown time limit 30 s with inverter.

 

Family series (1) Initiated by external emergency button with signal wire connected to the Inverter’s ELV circuit.

 

Family series (2) Initiated by the loss of AC Grid.

To the requirements of
UL 1741 (Second Edition; Reprint with Revisions Through and Including September 16, 2020)

Utility Interactive Microinverter

Model(s)Electric Rating
EZ1-LV and DS3-LVRefer Table

 

Model:

EZ1-LV

DS3-LV

INPUT RATINGS:

Maximum input voltage

60V

60V

Range of input operating voltage

26V-60V

26V-60V

Range of MPPT input operating voltage

27V-45V

27V-45V

Maximum input string

2

2

Maximum input current (dc)

18A (2 inputs)

18A (2 inputs)

Maximum input short circuit current

25A per input

25A per input

Maximum input source backfeed current to input source

0A

0A

OUTPUT RATINGS:  

Output power factor rating

>0.99 (-0.9~0.9 adjustable)

>0.99 (-0.9~0.9 adjustable)

Operating voltage range (ac) 1

105.6-132V

105.6-132V

Operating frequency range or single frequency1

59.3Hz-60.5Hz

59.3Hz-60.5Hz

Number of phases

Nominal output voltage (ac)

120Vac

120Vac

Normal output frequency

60Hz

60Hz

Maximum continuous output current (ac)

7.5A

7.5A

Maximum continuous output power (ac)

900VA

900VA

Maximum output fault current (ac) and duration

22.9Apk, 18.8ms of duration

 

22.9Apk, 18.8ms of duration

 

Maximum output overcurrent protection

16A

16A

Utility interconnection voltage and frequency trip limits and trip times

See Note 1 and Note 2 below

See Note 1 and Note 2 below

Trip limit and trip time accuracy

 

 

Voltage:

±2V

Frequency:

± 0.1 Hz

Alternate Trip Time

See Note 1 below

Normal operation temperature range

-40ºC + 65ºC

Maximum operating ambient

+65℃

Enclosure Rating Type

Type 6

 

Notes: 

 

  1. Utility Interconnection Voltage and Frequency Trip Limits and Trip Times:

 

Voltage and frequency limits for utility Interaction

 

Condition

Simulated utility source

Maximum time (sec) (cycles) at 60 Hza before cessation of current to the simulated utility

trip time accuracy

Voltage (V)

Frequency (Hz)

A

< 0.50 Vnor

Rated

0.08

+/-80ms

B

0.75Vnor ≤ V< 0.995Vnor

Rated

0.16-600

+/-200ms

C

1.004Vnor< V < 1.125 Vnor

Rated

0.16-600

+/-200ms

D

1.20 Vnor ≤ V

Rated

0.08

+/-80ms

E

60.1<f<62.0(adjustable)

f > 60.5

0.16

+/-200ms

F

57.0<f<59.9(adjustable)

f < 59.3

0.16

+/-200ms

Reconnection time accuracy: 30-600S +/-10s

 

  1. Utility interactive evaluations were conducted with the following firmware:

Inverter Model

Microprocessor/FPGA

Firmware

Checksum

EZ1-LV

DS3-LV

TMS320F2800xx

V1

9103CFA5

 

  1. Surge Testing for Combination Wave (1.2/50us) was done at 6 kV/3 kA, 2 ohms effective impedance, and Ringwave (0.5us-100 kHz) was done at 6 kV/0.5 kA, 12 ohms effective impedance.  Tests were performed using both polarities, for common mode and differential mode coupling, 20 pulses each test.  After surge testing the unit was operational with control functionally verified by frequency and voltage disconnect tests.

 

  1. This product's software has not been evaluated to the requirements of UL 1998.