Customer Class File Number
Weidmueller Interface GmbH & Co. KG
Klingenbergstrasse 26
Detmold
North Rhine-Westphalia
Germany
32758
5311-67
POWER SUPPLIES - Component Type (CSA 62368-1)
200039

Last Updated:

May 24, 2023 (Replaced: April 3, 2023)

To the requirements of
CSA C22.2 NO. 62368-1:19

DIN‑Rail Power Supply

ModelsOutput Voltage (V)Output Current (A)Input Voltage (V)Input Current (A max)ClassInput Frequency (Hz)Input Voltage
PRO BAS 30W 12V 2.6A122.6120‑3400.6II
1.0 50‑60100‑240 V~

ModelsInput Frequency (Hz)Output Voltage (V)Output Current (A)Input VoltageInput Current (A max)Input Voltage (V)Class
PRO BAS 30W 24V 1.3A50‑60241.3100‑240 V~1.0
0.6120‑340II
PRO BAS 60W 12V 5A50‑60125100‑240V~1.5
1.2120‑340II
PRO BAS 60W 24V 2.5A50‑60242.5100‑240V~1.5
1.2120‑340II
PRO BAS 120W 24V 5A50‑60245100‑240 V~4
3120‑340I

ModelsInput Voltage (V)Input Frequency (Hz)Input Current (A max)Output Voltage (V)Output Current (A)ClassInput Voltage
PRO BAS 30W 5V 6A120‑34050‑600.656II
1.0 100‑240V~

ModelsInput Voltage (V)Input Current (A max)Output Voltage (V)Output Current (A)ClassInput Frequency (Hz)Input Voltage
PRO BAS 90W 24V 3.8A120‑3401.5243.8II
2.5 50‑60100‑240 V~
PRO BAS 120W 12V 10A120‑34031210I
4 50‑60100‑240 V~

ModelsInput Frequency (Hz)Input Current (A max)Output Voltage (V)Output Current (A)Input VoltageInput Voltage (V)Class
PRO BAS 240W 24V 10A50‑6042410 100‑240 V~
4 120‑340I
PRO BAS 240W 48V 5A50‑604485100‑240 V~
4 120‑340I
PRO BAS 480W 48V 10A50‑6084810100‑240 V~
8 120‑340I

ModelsInput Frequency (Hz)Input Current (A max)Output Voltage (V)Output Current (A)Input VoltageClassInput Voltage (V)
PRO BAS 480W 24V 20A50‑6082420100‑240 V~
8 I120‑340

To the requirements of
CSA C22.2 NO. 62368-1:14

Component Power supply for DIN-Rail Power Supply

ModelsInput Voltage (V)Input Current (A)Output Voltage (V)Output Current (A)
PRO DCDC 96W 12V/12V 8A129.5128
PRO DCDC 120W 12V/24V 5A1211.8245

ModelsOutput Voltage (V)Output Current (A)Input Voltage (V)Input Current (A)
PRO DCDC 96W 24V/12V 8A128244.5
PRO DCDC 96W 48V/12V 8A128482.25
PRO DCDC 120W 48V/24V 5A245482.85

ModelsOutput Current (A)Input Voltage (V)Input Current (A)Output Voltage (V)
PRO DCDC 240W 24V/48V 5A52411.548

ModelsOutput Current (A)Output Voltage (V)Input Voltage (V)Input Current (A)
PRO DCDC 240W 48V/48V 5A548485.6

Conditions of Acceptability:

  1. The above models are certified only as components of other certified equipment, where the suitability of the combination is to be determined by CSA
  2. Transformer T1 use a min. Class B/130°C insulation system.
  3. Altitude during operation (m): ≤5000m.
  4. The product was tested in a branch circuit protected by a 20 A circuit breaker.  Additional evaluation shall be conducted if a higher protector is to be used in the end system. During all component fault testing, no external circuit breaker open.  Power supply is protected by the internal fuse or other internal circuit or mechanism.
  5. A suitable mechanical/ electrical and fire enclosure shall be provided in the end system, except for the front panel
  6. The max. operating temperature around the equipment under test is 70°C.
  7. The loading condition for the power supply at different input voltage and/or temperature is one of the following a) or b) or c):

    a) For AC input: the output current should be decreased 0.1%/V linearly when input voltage decreased from 100Vac to 90Vac; b) For DC input: the output current should be decreased 0.1%/V linearly when input voltage decreased from 120Vdc to 110Vdc;

    c) For operating temperature: the output current should be decreased 2.5%/°C from +55°C to +70°C.
  8. The AC input tolerance of the power supply is 90-264Vac, and DC input tolerance is 110-370Vdc.
  9. When installing the equipment, all requirements of the mentioned standard must be fulfilled.
  10.  Blocked of ventilation openings should be considered in end system.
  11.  For the purpose of spacing and insulation considerations, the DC input of this power supply shall be derived from the end system of maximum 240VAC mains supply.
  12.  For all models except PRO BAS 480W 24V 20A and PRO BAS 480W 48V 10A, 4000 Vdc hi-pot test is conducted between the isolated voltage input and enclosure/all other secondary outputs. For PRO BAS 480W 24V 20A and PRO BAS 480W 48V 10A, 2500 Vdc hi-pot test is conducted between the isolated voltage input and enclosure/all other secondary outputs.
  13.  The electric strength in the end product shall be based on the value for maximum working voltage between primary and secondary.
  14.  For models PRO BAS 30W 12V 2.6A, PRO BAS 30W 24V 1.3A, PRO BAS 30W 5V 6A, PRO BAS 60W 12V 5A, PRO BAS 60W 24V 2.5A, PRO BAS 90W 24V 3.8A, the maximum Output complied with Class 2 output according to ANSI/UL 1310, 7th Ed and CSA-C22.2 No. 223-15.