Customer Class File Number
ERICO International Corporation
34600 Solon Rd
Solon
Ohio
United States
44139
6228-01
WIRE CONNECTING DEVICES - Terminal Assemblies
160371

To the requirements of
CSA C22.2 NO. 158-10

WIRE CONNECTING DEVICES‑Terminal Assemblies

Model(s)Current (A max)GroupTorqueVoltage (V)Wire Range
Cat No. 561132255C221 in‑lbs1000No 8‑250 kcmil 

Note: * 200A rating for Cat Nos 569051, 569251 is based on one No 3/0 AWG wire connected to one of the line terminal and the other line terminal being used with manufacturer's jumper wire Cat No 569200 to connect multiple poles in series. 

Model(s)Current (A max)GroupTorqueVoltage (V)Wire Range
Cat No. 561134475C265 in‑lbs1000No 6‑750 kcmil            
Cat No. 561136  760C265 in‑lbs1000 2x No 4‑500 kcmil, (line )/  2x No 4‑500 kcmil, (load )
Cat No. 561140300C221 in‑lbs10002x No 6‑250 kcmil, line
168 in‑lbs 2x No 8‑2/0 AWG, load
Cat No. 561142310C221 in‑lbs1000No 2‑350 kcmil
Cat No. 561143310C221 in‑lbs1000No 2‑350 kcmil
Cat No. 561144500C265 in‑lbs10002x No 6‑700 kcmil, line
168 in‑lbs 2x No 6‑250 kcmil, load
Cat No. 561146760C265 in‑lbs10002x No 4‑500 kcmil, line
300 in‑lbs 2x 3/0‑500 kcmil, load
Cat no. 569051400C120 in‑lbs10002x No 3/0‑8 AWG, line
200A* 120 in‑lbs No 3/0‑8 AWG, line
65 24 in‑lbs 12x No 14‑6 AWG, load
Cat No. 569052335C221 in‑lbs1000No 3/0‑400 kcmil, line
65 24 in‑lbs 12x No 14‑6 AWG, load
Cat No. 569251400C120 in‑lbs10002x No 3/0‑8 AWG, line
200A* 120 in‑lbs No 3/0‑8 AWG, line
65 45 in‑lbs 12x No 14‑6 AWG, load
Cat No. 569252335C221 in‑lbs1000No 3/0‑400 kcmil, line
65 45 in‑lbs 12x No 14‑6 AWG, load
Cat No. 561147760C300 in‑lbs10002x No 3/0‑ 500 kcmil

Note: * 200A rating for Cat Nos 569051, 569251 is based on one No 3/0 AWG wire connected to one of the line terminal and the other line terminal being used with manufacturer's jumper wire Cat No 569200 to connect multiple poles in series.

Model(s)Current (A max)GroupTorqueVoltage (V)Wire Range
Cat No. 561145 500C168 in‑lbs10002x No 6‑250 kcmil

Note: * 200A rating for Cat Nos 569051, 569251 is based on one No 3/0 AWG wire connected to one of the line terminal and the other line terminal being used with manufacturer's jumper wire Cat No 569200 to connect multiple poles in series

Model(s)Current (A max)GroupTorqueVoltage (V)Wire Range
Cat No. 56901085B, C19.5 in‑lbs600No 16‑4 AWG, line
50 10.6 in‑lbs No 16‑8 AWG, load, top
85 19.5 in‑lbs No 16‑4 AWG, load, bottom 
Cat No. 569020150B, C57 in‑lbs600No 8‑1/0 AWG, line
115 31 in‑lbs No 14‑2 AWG, line/load (Jumper)
115 31 in‑lbs No 14‑10 AWG, line/load (Jumper)
85 31 in‑lbs No 10‑4 AWG, load
Cat No. 569030200B, C75 in‑lbs600No 8‑3/0 AWG, line
115 31 in‑lbs No 14‑2 AWG, line/load (Jumper)
115 31 in‑lbs No 14‑10 AWG, line/load (Jumper)
85 31 in‑lbs No 10‑4 AWG, load
Cat No. 569040255B, C168 in‑lbs600No 6‑250 kcmil, line
85 24 in‑lbs No 8‑4 AWG, load, top
65 24 in‑lbs No 8‑6 AWG, load, middle 
130 39 in‑lbs No 8‑1 AWG, load, bottom
Cat No. 569050355B, C221 in‑lbs600No 3/0‑400 kcmil, line
85 24 in‑lbs No 8‑4 AWG, load, top
65 24 in‑lbs No 8‑6 AWG, load, middle
130 39 in‑lbs No 8‑1 AWG, load, bottom

To the requirements of
CSA C22.2 No. 158:10 (R2019)

DIN Rail Splice Terminal Blocks for use with solid or stranded copper conductors

Model(s)CurrentVoltageGroupWire Range LineTightening TorqueWire Range LoadTightening Torque
561132255A1000VC8AWG ‑ 250MCM221 in‑lbs8AWG ‑ 250MCM221 in‑lbs
561134475A1000VC6AWG ‑ 750MCM265 in‑lbs6AWG ‑ 750MCM265 in‑lbs
561136760A1000VC(2x) 4AWG ‑ 500MCM265 in‑lbs(2x) 4AWG ‑ 500MCM265 in‑lbs
561140300A1000VC(2x) 6AWG ‑ 250MCM221 in‑lbs(2x) 8AWG ‑ 2/0AWG168 in‑lbs
561141300A1000VC(2x) 8AWG ‑ 1/0AWG168 in‑lbs(2x) 8AWG ‑ 1/0AWG168 in‑lbs
561142310A1000VC2AWG ‑ 350MCM221 in‑lbs2AWG ‑ 350MCM221 in‑lbs
561143310A1000VC2AWG ‑ 350MCM221 in‑lbs2AWG ‑ 350MCM221 in‑lbs
561144500A1000VC(2x) 6AWG ‑ 700MCM265 in‑lbs(2x) 6AWG ‑ 250MCM168 in‑lbs
561145500A1000VC(2x) 6AWG ‑ 250MCM168 in‑lbs(2x) 6AWG ‑ 250MCM168 in‑lbs
561146760A1000VC(2x) 4AWG ‑ 500MCM265 in‑lbs(2x) 3/0AWG ‑ 500MCM300 in‑lbs
561147760A1000VC(2x) 3/0AWG ‑ 500MCM300 in‑lbs(2x) 3/0AWG ‑ 500MCM300 in‑lbs
56115085A1000VC16AWG ‑ 4AWG (STR)19.5 in‑lbs16AWG ‑ 4AWG (STR)19.5 in‑lbs
"""16AWG ‑ 10AWG (SOL)19.5 in‑lbs16AWG ‑ 10AWG (SOL)19.5 in‑lbs
561151200A1000VC2AWG ‑ 3/0AWG95 in‑lbs2AWG ‑ 3/0AWG95 in‑lbs
561152335A1250VC3/0AWG ‑ 400MCM 264 in‑lbs3/0AWG ‑ 400MCM264 in‑lbs
561156545A1250VC400MCM ‑ 1000MCM400 in‑lbs400MCM ‑ 1000MCM400 in‑lbs
561158150A1250VC8AWG ‑ 1/0AWG57 in‑lbs8AWG ‑ 1/0AWG57 in‑lbs
561159255A1250VC6AWG ‑ 250MCM168 in‑lbs6AWG ‑ 250MCM168 in‑lbs
56116085A1000VC16AWG ‑ 4AWG (STR)19.5 in‑lbs16AWG ‑ 4AWG (STR)19.5 in‑lbs
"""16AWG ‑ 10AWG (SOL)19.5 in‑lbs16AWG ‑ 10AWG (SOL)19.5 in‑lbs
561161150A1250VC8AWG ‑ 1/0AWG57 in‑lbs8AWG ‑ 1/0AWG57 in‑lbs
561162200A1000VC2AWG ‑ 3/0 AWG95 in‑lbs2AWG ‑ 3/0 AWG95 in‑lbs
561163255A1250VC6AWG ‑ 250MCM168 in‑lbs6AWG ‑ 250MCM168 in‑lbs
561164335A1250VC3/0AWG ‑ 400MCM264 in‑lbs3/0AWG ‑ 400MCM264 in‑lbs
561168545A1250VC400MCM ‑ 1000MCM400 in‑lbs400MCM ‑ 1000MCM400 in‑lbs

DIN Rail Distribution Terminal Blocks for use with solid or stranded copper conductors

Model(s)CurrentVoltageGroupTerminalsWire RangeTightening Torque
563995250A600VB, CLine8AWG ‑ 250MCM177 in‑lbs
"""Load ‑ 9.5mm wire entry6AWG ‑ 1/0AWG 75 in‑lbs
"""Load ‑ 9mm wire entry8AWG ‑ 1AWG57 in‑lbs
"""Load ‑ 7mm wire entry10AWG ‑ 3AWG (Stranded)31 in‑lbs
"""Load ‑ 7mm wire entry10AWG ‑ 6AWG (Solid)31 in‑lbs
"""Load ‑ 5.5mm wire entry10AWG ‑ 5AWG (Stranded)24 in‑lbs
"""Load ‑ 5.5mm wire entry10AWG ‑ 6AWG (Solid)24 in‑lbs
56901085A600VB, CLine16AWG ‑ 4AWG19.5 in‑lbs
50A600VB, CLoad ‑ Top16AWG ‑ 8AWG10.6 in‑lbs
85A600VB, CLoad16AWG ‑ 4AWG19.5 in‑lbs
569020150A600VB, CLine8AWG ‑ 1/0AWG57 in‑lbs
115A600VB, CLine/Load ‑ Jumper14AWG ‑ 2AWG31 in‑lbs
115A600VB, CLine/Load ‑ Jumper14AWG ‑ 10AWG31 in‑lbs
85A600VB, CLoad10AWG ‑ 4AWG31 in‑lbs
569030200A600VB, CLine8AWG ‑ 3/0AWG75 in‑lbs
115A600VB, CLine/Load ‑ Jumper14AWG ‑ 2AWG31 in‑lbs
115A600VB, CLine/Load ‑ Jumper14AWG ‑ 10AWG31 in‑lbs
85A600VB, CLoad10AWG ‑ 4AWG31 in‑lbs
569040255A600VB, CLine6AWG ‑ 250MCM168 in‑lbs
85A600VB, CLoad ‑ Top8AWG ‑ 4AWG24 in‑lbs
65A600VB, CLoad ‑ Middle8AWG ‑ 6AWG24 in‑lbs
130A600VB, CLoad ‑ Bottom8AWG ‑ 1AWG39 in‑lbs
569050355A600VB, CLine3/0AWG ‑ 400MCM221 in‑lbs
85A600VB, CLoad ‑ Top8AWG ‑ 4AWG24 in‑lbs
65A600VB, CLoad ‑ Middle8AWG ‑ 6AWG24 in‑lbs
130A600VB, CLoad ‑ Bottom8AWG ‑ 1AWG39 in‑lbs
569051400A1000VCLine(2x) 8AWG ‑ 3/0AWG120 in‑lbs
200A1000VCLine8AWG ‑ 3/0AWG120 in‑lbs
65A1000VCLoad(12x) 14AWG ‑ 6AWG24 in‑lbs
569052335A1000VCLine3/0AWG ‑ 400MCM221 in‑lbs
65A1000VCLoad(12x) 14AWG ‑ 6AWG24 in‑lbs
569251400A1000VCLine(2x) 8AWG ‑ 3/0AWG120 in‑lbs
200A1000VCLine8AWG ‑ 3/0AWG120 in‑lbs
65A1000VCLoad(12x) 14AWG ‑ 6AWG45 in‑lbs
569252335A1000VCLine3/0AWG ‑ 400MCM221 in‑lbs
65A1000VCLoad(12x) 14AWG ‑ 6AWG45 in‑lbs

Notes

  1. These terminal blocks are supplied only to manufacturers, as components, for the assembly of Certified electrical equipment, where the suitability of the combination in the end use is determined by CSA Group. 
  2. Suffixes
  3. 200A rating for Cat Nos 569051, 569251 is based on one No 3/0 AWG wire connected to one of the line terminal and the other line terminal being used with manufacturer's jumper wire Cat No 569200 to connect multiple poles in series.