Customer Class File Number
Wöhner GmbH & Co. KG
Mönchrödener Str 10
Rödental
Bavaria
Germany
96472
3211-37
INDUSTRIAL CONTROL EQUIPMENT - Sub-Assemblies - Components
110285_0_000

 

  1. TO THE REQUIREMENTS OF STANDARD C22.2 NO 14-13

    Bus Bar Supports, Type Nos. 484, 485, 495, 496, 497, 498 and 499.

    Bus Bar Supports, Type Nos. S610 and S620-L.

    Base Plate Insulation, Type No. B620-L.

    Bus Bars, Type Nos. 12x5-L, 12x10-L, 20x5-L, 20x10-L, 30x5-L and 30x10-L.

    Bus Bar End Cover, Type No. 511-L.

    Bus Bar Support for Ground Bus Bar, Type No. 489-L.

    Double T Bus Bar Support, Type No. S630-L.

    Double T Bus Bars, Type Nos. H500-L and H720-L.

    Triple T Bus Bar Support, Type No. S640-L.

    Triple T Bus Bar, Type No. HH1140-L.

    Double and Triple T Bus Bar End Cover, Type No. 234-L.

    Double T Bus Bar Support for Ground Bus Bar, Type No. 876-L.

    Power Terminals, Type Nos. 521, 522, 523, 524, 525, 526, 527 and 528.

    Power Terminals, Type Nos. 518, 529, 519 and 530.

    Power Terminals, Type Nos. H41.2, H51.1 and H51.2, Terminal Cover, Type No. CH51.

    Power Terminals, Type Nos. H64.1, H64.2 and H81.2, Terminal Cover, Type No. CH81.

    Power Terminal, Type No. H101.2, Terminal Cover, Type No. CH101.

    Power Terminal, Type No. HH41.2, Terminal Cover, Type No. CHH41.

    Power Terminal, Type No. HH64.2, Terminal Cover, Type No. CHH64.

    Power Terminal, Type No. HH101.2, Terminal Cover, Type No. CHH101.

    Power Terminal Assembly (3-pole), Type Nos. 412 and 413.

    Power Terminal Assembly (3-pole), Type Nos. 240-L and 243-L.

    Power Terminal Assembly (L1+L2+L3-Pole), Type Nos. M185, M300-L and M3210-L.

    Shoes (Bus Bar Adapters), Type Nos. 4012, 4025, 4025.1, 4025.2, 4032, 4050.1, 4063, 4080, 4080.1, 4610.1, 6012, 6025, 6025.1, 6032, 6050.1, 6063, 6080, 6016, 40160.1, 40160.2, 60160.1, 60160.2, 60200, 60250, 60250.1-L, 60250.2 and 60630.1-L.

    Bus Bar Adapters without power, Type Nos. 4000, 6000.

    Bus Bar Adapter Modules, Type Nos. 480.1 and 680.1.

    Bus Bar Adapter Modules, Type Nos. 4016.1 and 6016.1.

    Connecting Clip, Type No. 79475.

    Shoes (Bus Bar Adapters), Type Nos. EEC6025-L, EEC6032-L, EEC6063-L, EEC6080-L, EEC6090, EMC6025-L, EMC6032-L and EMC6045-L.

    Terminal Extensions, Type Nos. EEC25-L and EEC80-L.

    Bus Bar Adapters without power, Type Nos. EEC6000-L and EMC6000-L.

    Connecting Clip, Type No. X-L.

    Bus Bar Covers, Type Nos. 500 and 501, Cover for Blank Field, Type No. 509, Power Terminal Cover, Type Nos. 502, 503, 512 and 513, Bus Bar Support Covers, Type Nos. 504 and 505, Channel Snap Mounts, Type No. 506, Cover Channel, Type Nos. 507 and 508.

    Bus Bar Covers, Type Nos. C30x5-L, C30x10-L and CHH-L.

    Cover Assembly, Type No. CTC60-L.

    Cover Support, Type No. TC60-L, Cover Profiles, Type Nos. C60.1-L and C60.2-L.

    Cover Support, Type No. C026-L, Cover for Blank Field, Type No. C025-L.

    Combination Plates for DIN Rail and Screw Mounting without Electrical Contents, Type No. EEP.

    Mounting Rail, Type No. TS35-L.

    Panel mounted Class J fuseholder, cartridge type, 3 pole Cat Nos JC100, JC200 and JC400, 100, 200 and 400A, respectively, 600V ac.

    Bus mounted Class J fuseholder, cartridge type, 3 pole, Cat Nos JC100B, JC200B and JC400B, 100, 200 and 400A, respectively, 600V ac.

    Busbar mounted Class CC and 10x38 fuseholder, 3 pole, Cat Nos AEL 10x38 and AEL CC, 30A, 600V

     

    Notes:

    1. The ratings of the control equipment shall not exceed the rating of the subject device.

    2. The temperature rise on the connecting straps shall not exceed 65C rise at an ambient temperature of 40C max.  Consideration should be given in the end product to determine if a repeat of the Temperature Test is necessary.

    3. These devices should be mounted in an enclosure having adequate dimensions and thickness in the intended manner and with suitable spacings provided in accordance with the end use.

    4. The application of the covers does not justify the reduction of the electrical spacings through air or over surface.

    5. These devices have not been investigated for make/break operations, and shall be investigated as part of the ultimate application.

    6. These devices were subject to 5 and 10kA, 600V ac and 42kA, 480V ac Short Circuit Tests. A determination should be made in the end application if a Short Circuit Test should be performed.

    7. Busbar Support 484 is provided with wiring terminals, however, it is intended for use as an end of run busbar support with the terminals intended for factory connection to control circuit devices only. 

       The control circuit devices shall be provided    with overcurrent and short circuit protection.

    8. The suitability of the bus bar terminals for Type No. 4610.1 has not been evaluated with respect to secureness, pullout, or the ability of the device which is mounted to the adapter to accommodate the bus bar terminals. 

        This should be evaluated  in the end use application.

    9. Fuseholder, Cat Nos JC100, JC200, JC400 are to be mounted on a panel in an enclosure with min dimensions of 72 by 36 by 12 in.  These devices were subjected to a 200kA, 600V ac short circuit test.

    10. Fuseholder, Cat No JC100B, JC200B are to be mounted on 10 by 20mm bus bar system. Fuseholder, Cat No JC400B are to be mounted on 10 by 30mm bus bar system.  These devices were subjected to a 65kA, 600V ac short circuit test.

    11. The power terminal assembly Type 240-L is rated 195A and Type 243-L is rated 400A.

    12. Fuseholder, Cat No AEL 10x38 and AEL CC are to be mounted a bus bar system. These devices were subjected to a 50kA resp. 200kA, 600V ac short circuit test and are suitable for use with 16-10 AWG copper wire only

     