Customer Class File Number
Cummins Generator Technologies Limited
Fountain Court, Lynch Wood
Peterborough
Cambridgeshire
United Kingdom
PE2 6FZ
4211-01
MOTORS AND GENERATORS - Motors and Generators
011305_0_000


Synchronous generators, rotating field, brushless, self‑excited, guarded and dripproofsingle

Model(s)PhaseFrequency (Hz)Voltage (V max)Insulation Class Power
Frame PCL1Single or 3 50‑60600H22.5kVA max continuous
Frame PC1, Frame CC2 to FrameCC7Single or 3 50‑60600H1875kVA max continuous, 2000kVA max standby
CM rangeSingle or 3 50‑604160F1500kW max continuous

Notes:

  1. The complete type designation consists of the frame size followed possibly by figures indicating method of excitation, the number of poles and number of bearings and followed by letters denoting different core lengths.
  2. Synchronous generators for incorporating in generating sets
  3. Machines may be fitted with anti-condensation heaters and/or temperature detectors.

Model(s)PhaseFrequency (Hz)Insulation Class Voltage (V max)Power
Frames HC4 to Frames HC7Single or 3 50‑60H6902500kW max continuous, 2600kW max standby
HCK4-HCK7Single or 3 50‑60H6902500kVA continuous, 2688kVA standby

Notes:

  1. The complete type designation consists of the frame size followed possibly by figures indicating method of excitation, the number of poles and number of bearings and followed by letters denoting different core lengths.
  2. Synchronous generators for incorporating in generating sets may be supplied without terminal boxes subject to the acceptability of the combination to CSA Group.
  3. Machines may be fitted with anti-condensation heaters and/or temperature detectors.

Model(s)PhaseFrequency (Hz)Voltage (V)Power
UCD range ACO 224, 274Single or 3 50‑60600300kVA maximum 319kVA maximum standby

Notes:

  1. The complete type designation consists of the frame size followed possibly by figures indicating method of excitation, the number of poles and number of bearings and followed by letters denoting different core lengths.
  2. Synchronous generators for incorporating in generating sets may be supplied without terminal boxes subject to the acceptability of the combination to CSA Group.
  3. Machines may be fitted with anti-condensation heaters and/or temperature detectors.

Model(s)PhaseFrequency (Hz)FrameVoltage (V)Insulation Class Power
BC, BCA, BCL rangesSingle or 3 50‑6016 and 18600H37.5kVA max continuous

Notes:

  1. The complete type designation consists of the frame size followed possibly by figures indicating method of excitation, the number of poles and number of bearings and followed by letters denoting different core lengths.
  2. Synchronous generators for incorporating in generating sets may be supplied without terminal boxes subject to the acceptability of the combination to CSA Group.
  3. Machines may be fitted with anti-condensation heaters and/or temperature detectors.

AC Generators, Rotating Field, Self‑Excited, Brushless, Drip‑proof

Model(s)FramePole(s)Voltage (V max)PhaseFrequency (Hz)PowerInsulation Class
B105 rangeA to E2240Single 607kW max. at unity Power FactorF

Note: The generators are supplied without terminal boxes for incorporating in generating sets, subject to the combinations being acceptable to CSA Group.

AC Generators, Rotating Field, Self‑Excited, Drip‑proof

Model(s)Pole(s)Voltage (V max)PhaseFrequency (Hz)PowerInsulation Class Frame
SD105 Range2240Single 608.5kW max. at unity Power FactorFA to F

Note: The generators are supplied without terminal boxes for incorporating in generating sets, subject to the combinations being acceptable to CSA Group.

AC Generators, Rotating Field, Self‑Excited, brushless, drip proof

Model(s)Pole(s)Voltage (V max)PhaseFramePowerInsulation Class
BL105 range2240Single A to G7.5kW max, at unity power factorH

Note: The generators are supplied without terminal boxes for incorporating in generating sets, subject to the combinations being acceptable to CSA Group.

AC Generators, Rotating Field, Self‑Excited, drip proof

Model(s)Pole(s)Voltage (V max)PhaseFrameInsulation Class Frequency (Hz)Power
SL105 range2240Single A to GH609.3kW max, at unity power factor

Note: The generators are supplied without terminal boxes for incorporating in generating sets, subject to the combinations being acceptable to CSA Group.

Model(s)Pole(s)Insulation Class Frequency (Hz)FrameVoltage (V max)PhasePower
TL105 range2H60E to G440Three8.75kVA max, at unity power factor

Note: The generators are supplied without terminal boxes for incorporating in generating sets, subject to the combinations being acceptable to CSA Group.

Synchronous Generator, rotating field, brushless, self‑excited, drip‑proof

Model(s)Voltage (V max)PhaseFrequency (Hz)Insulation Class Power
Frame LVSI814690Three50/60HMaximum continuous 3375kVA, Maximum continuous standby 3638kVA

Notes:

  1. The complete type designation consists of the frame size as detailed above, followed by other figures and a letter indicating the core length.
  2. Generators may be fitted with anti-condensation heaters and/or temperature detectors.

Synchronous Generators, rotating field, brushless, self excited, guarded or drip‑proof

Model(s)Voltage PhaseFrequency (Hz)ClassPower
Frame MV7From 751V up to 4160V maxThree50/60F2188kVA maximum continuous

Notes:

  1. The complete type designation consists of the frame size as detailed above, followed by other figures and a letter indicating the core length.
  2. Generators may be fitted with anti-condensation heaters and/or temperature detectors.

Synchronous generators, brushless, self‑excited, drip‑proof

Model(s)Voltage (V max)PhasePole(s)
Frame P7600Three4

Rated 50/60Hz, 2800 kVA max continuous, 3120 kVA max standby, maximum ambient temperature 27º or 40ºC, Class H, and 6-pole, rated 50/60Hz, 1695 kVA max continuous, 1815 kVA max standby, maximum ambient temperature 27º or 40ºC, Class H.

Notes:

  1. The complete type designation consists of the frame size as detailed above, followed by other figures and a letter indicating the core length.
  2. Generators may be fitted with anti-condensation heaters and/or temperature detectors.

Model(s)Voltage (VAC max)PhasePole(s)Frequency (Hz)PowerAmbient Temp (°C max)Class
Frame S4690Single and three4 50/60 560 kVA max continuous, 625 kVA max standby27 or 40H

Model(s)Pole(s)Frequency (Hz)Ambient Temp (°C max)ClassVoltage (VAC max)PhasePower
Frame S64 50/60 27 or 40H600Three1694 kVA max continuous, 1812 kVA max standby

Model(s)Pole(s)Frequency (Hz)Ambient Temp (°C max)ClassPhaseVoltage (VAC max)Power
Frame S54 50/60 27 or 40HThree690937 kVA max continuous, 1013 kVA max standby

Synchronous generators, rotating field, brushless, self‑excited, guarded or drip‑proof, 0.8 P.F. Class H for ratings up to 4160V and Class F for ratings over 4160V

Model(s)Voltage (V max)PowerTemperature (°C)PhaseFrequency (Hz)
Frame LV80, Frame MV80, Frame HV80380 to 138005190kVA max, 4152kW max40Three50/60

Notes:

  1. The complete type designation consists of the frame size as detailed above, followed by other figures and a letter indicating the core length.
  2. Generators may be fitted with anti-condensation heaters and/or temperature detectors.

Synchronous generators, rotating field brushless, self‑excited, totally enclosed air to air cooled, 0.9 P.F., Class H for 4160V and Class F for ratings over 4160V

Model(s)Voltage PowerTemperature (°C)PhaseFrequency (Hz)
Frame W80From 4160V to 13800V max2222kVA max, 2000kW max40Three50/60

Notes:

  1. The complete type designation consists of the frame size as detailed above, followed by other figures and a letter indicating the core length.
  2. Generators may be fitted with anti-condensation heaters and/or temperature detectors.

Brushless Synchronous Generators, 0.8 P.F., guarded and drip proof, self excited

Model(s)PowerVoltage (VAC)PhaseFrequency (Hz)Ambient Temp (°C)ClassSpeed (RPM)
PI0 series, PI1 series4.5kVA to 55 kVA continuous, 5.0kVA to 60kVA standby600Three or Single50/60 27 or 40 H1500/1800 and 3000/3600

Notes:

  1. The complete designation consists of the frame size, as detailed above, followed by other figures indicating number of poles, number of bearings and a letter indicating core length.
  2. The generators may be supplied without terminal boxes for incorporating in generating sets, subject to the acceptability of the combination to CSA Group.
  3. Generators may be fitted with anti-condensation heaters and/or temperature detectors.
  4. Generators may be fitted with an EBS (Excitation Boost System).

Model(s)Cord LengthVoltage (V max)Power
Frame HC4 to Frame HC5C to F480825 kVA max continuous

Conditions of Acceptability:

  1. These generators are certified only as a component for use in generator sets and the acceptability of these generators in end use application are to be determined by local inspection authority.
  2. The above generators are evaluated with a prime mover end belts that encloses the impellers or fan blades of the generators so that these fan blades are not accessible with the use of a test probe having a diameter of 12.7mm.
  3. The generators outputs are to be protected against overloads as per the local electrical codes.
  4. Provision for earthing is made on Terminal Box as well as on machine body and the earthing of machine is to be done in as per the instruction provided in the Installation and service manual which is provided as an accompanying document with each machine. (ref annexure-I)

Model(s)Voltage (V max)Cord LengthPowerPhasePower (kVA max)
Frame UC22 to Frame UC27480C to H255 kVA maximum continuous3
480C to H 1156.3

Conditions of Acceptability:

  1. These generators are certified only as a component for use in generator sets and the acceptability of these generators in end use application are to be determined by local inspection authority.
  2. The above generators are evaluated with a prime mover end belts that encloses the impellers or fan blades of the generators so that these fan blades are not accessible with the use of a test probe having a diameter of 12.7mm.
  3. The generators outputs are to be protected against overloads as per the local electrical codes.
  4. Provision for earthing is made on Terminal Box as well as on machine body and the earthing of machine is to be done in as per the instruction provided in the Installation and service manual which is provided as an accompanying document with each machine. (ref annexure-I)

Model(s)Voltage (V max)Cord LengthPowerPhaseVoltage (V)Power (kVA)
Frame BC16 to Frame BC18480A to J50 kVA maximum continuous 3
A to J 124035

Conditions of Acceptability:

  1. These generators are certified only as a component for use in generator sets and the acceptability of these generators in end use application are to be determined by local inspection authority.
  2. The above generators are evaluated with a prime mover end belts that encloses the impellers or fan blades of the generators so that these fan blades are not accessible with the use of a test probe having a diameter of 12.7mm.
  3. The generators outputs are to be protected against overloads as per the local electrical codes.
  4. Provision for earthing is made on Terminal Box as well as on machine body and the earthing of machine is to be done in as per the instruction provided in the Installation and service manual which is provided as an accompanying document with each machine. (ref annexure-I)

Component open type Synchronous generators, rotating field, brushless, self‑excited/separately excited, single/two bearing configurations, PF 0.8 to 1.0

Model(s)Frequency (Hz)Insulation Class Speed (RPM)Ambient Temp (°C)Voltage (V max)PowerPhasePower (kVA)
Frame CA115, Frame CA125, Frame CA13560H1800 or 3600 4060075 kVA maximum continuous 3
60H1800 or 3600 40240 160

Conditions of Acceptability:

  1. These generators are certified only as a component for use in generator sets and the acceptability of these generators in end use application with certified/approved enclosure are to be determined by local inspection authority
  2. The generators outputs are to be protected against overloads as per the local electrical codes.
  3. Provision  for grounding is made on the terminal box as well as on machine body and the grounding of the machine is to be done in as per the instruction provided in the Installation and service manual which is provided as an accompanying document with each machine.
  4. This machine has provision for anti-condensation heaters, AVR, metering current transformers, Excitation boost controller, Thermistor, RTD, circuit breaker harness and main terminal box. This may be included as per end user requirement but do not fall in the scope of the certification.

Model(s)Frequency (Hz)Insulation Class Speed (RPM)Ambient Temp (°C)Voltage (V max)PowerPhasePower (kVA)
Frame CA115, Frame CA125, Frame CA13560H1800 or 3600 4060075 kVA maximum continuous 3
60H1800 or 3600 40240 160

Conditions of Acceptability:

  1. These generators are certified only as a component for use in generator sets and the acceptability of these generators in end use application with certified/approved enclosure are to be determined by local inspection authority
  2. The generators outputs are to be protected against overloads as per the local electrical codes.
  3. Provision for grounding is made on the terminal box as well as on machine body and the grounding of the machine is to be done in as per the instruction provided in the Installation and service manual which is provided as an accompanying document with each machine.
  4. This machine has provision for anti-condensation heaters, AVR, metering current transformers, Excitation boost controller, Thermistor, RTD, circuit breaker harness and main terminal box. This may be included as per end
  5. user requirement but do not fall in the scope of the certification.

Three phase synchronous generators, guarded or drip‑proof, 0.8 PF

Model(s)Power (kVA)Voltage (VAC)Frequency (Hz)Pole(s)ClassAmbient Temp (°C max)
Type DIG110, 120, 130, 140, 150 and 1561080 to 11,2003300 to 13,80050/604 to 10 F40
Type DSG62, 74, 86, 99, 114, 125 and 144600 to 8500400 to 69050/60 4 to 10H40

Notes: 
1. The complete designation consists of the frame series, voltage, lamination size (within family series), as detailed above, followed by other figures indicating stack length / diameter ratio and number of bearings.
2. Generators may be fitted with anti-condensation heaters and/or temperature detectors.
3. Generators may be supplied without AVR and need for additional evaluation in end application.

Synchronous generators, brushless, self‑excited, drip‑proof, 600V max, three phase 4‑pole

Model(s)Frequency (Hz)PowerAmbient Temp (°C max)Voltage (V max)Pole(s)PhaseAmbient Temp (°C)Class
S0L1 series, S0L2 series, S1L2 series50/60 76.5 kVA max continuous, 82.5 kVA max standby27 or 402404 Single
50/60 47.8kVA max continuous at 0.8 pf & 55.5 kVA at 1.0 pf , max standby 51.6 kVA 0.8 pf & 59.8 kVA at 1.0 PF 27 or 40H

Notes: 
1. The complete designation consists of the frame series, voltage, lamination size (within family series), as detailed above, followed by other figures indicating stack length / diameter ratio and number of bearings.
2. Generators may be fitted with anti-condensation heaters and/or temperature detectors.
3. Generators may be supplied without AVR and need for additional evaluation in end application.

To the requirements of
CSA C22.2 No. 100-14 (Upd.1 April 2017)(Seventh Edition) (R2019)

Synchronous generators, rotating field, brushless, self‑excited/separately excited, guarded and drip proof, 3 ph, 50‑60Hz, Class H insulation, single/two bearing configurations, 1500/1800rpm, 40ºC ambient. Frames HC4 to HC5, Core lengths C to F, 480V max, 825 kVA max continuous.

Model(s)PhaseFrequency (Hz)Rotational Speed (RPM)Ambient Temp (°C)Output Voltage (V max)Output Power (kVA max)
HC Series350/601500/180040480825

Synchronous generators, rotating field, brushless, self‑excited/separately excited, guarded and drip proof, single or 3 ph, 50‑60Hz, Class H insulation, single/two bearing configurations, 1500/1800rpm, 40ºC ambient, PF 0.8. Max ratings as follows:Frame UCI224: core lengths C to G, 480V max, 103.8 kVA maximum continuous for 3 phase, and 70 kVA max for 1 phase.Frame UCI274, core lengths C to H, 600V max, 255 kVA maximum continuous, for 3 phase and 156.3 kVA max for 1 phase.Frame UCDI274, core length J & K, 600V max 312.5 kVA maximum continuous, for 3 phase and 200 kVA max for 1 phase.

Model(s)PhaseFrequency (Hz)Rotational Speed (RPM)Ambient Temp (°C)Output Voltage (V max)Output Power (kVA max)Output Power (kVA max)Power Factor
UC Series1 or 350/601500/180040480103.8 (3 Ph) 70 (1 Ph)0.8
1 or 350/601500/180040600255 (3 Ph) 156.3 (1 Ph)0.8
1 or 350/601500/180040600312.5 (3 Ph) 200 (1 Ph) 0.8

Synchronous generators, rotating field, brushless, self‑excited, guarded and drip proof, single or 3 ph, 50‑60Hz, Class H insulation, single/two bearing configurations, 1500/1800rpm, 40ºC ambient. Frames BC16 to BC18, core lengths A to J, 480V max, 50 kVA maximum continuous for 3 phase and 240V, 35kVA for 1 phase.

Model(s)PhaseFrequency (Hz)Rotational Speed (RPM)Ambient Temp (°C)Output Voltage (V max)Output Power (kVA max)Output Power (kVA max)Power Factor
BC Series1 or 350/601500/180040480/24050 (3 Ph) 35 (1 Ph)0.8

Synchronous generators, rotating field, brushless, self‑excited/separately excited, guarded and drip proof, single or 3 ph, 50‑60Hz, Class H insulation, single/two bearing configurations, 1500/1800rpm or 3000/3600 rpm, 40ºC ambient, PF 0.8 to 1.0 Frames PI0 to PI1, 480V max, core lengths D to K, 53 kVA maximum continuous for 3 phase and 240V max, 34 kVA for 1 phase

Model(s)PhaseFrequency (Hz)Rotational Speed (RPM)Ambient Temp (°C)Output Voltage (V max)Output Power (kVA max)Output Power (kVA max)Power Factor
PI0/PI1 Series1 or 350/601500/1800 or 3000/360040480/24053 (3 Ph) 34 (1 Ph)0.8 to 1

Notes:

1. These generators are certified only as a component for use in generator sets and the acceptability of these generators in end use application are to be determined by local inspection authority.
2. The above generators are evaluated with a prime mover end belts that encloses the impellers or fan blades of the generators so that these fan blades are not accessible with the use of a test probe having a diameter of 12.7 mm.
3. The generators outputs are to be protected against overloads as per the local electrical codes.
4. Provision for grounding is made on the terminal box as well as on machine body and the grounding of the machine is to be done in as per the instruction provided in the Installation and service manual which is provided as an accompanying document with each machine. (See Annexure-I). 

Synchronous generators, Frame S7 brushless, self‑excited, drip‑proof, 690V ac max, three phase, 4‑pole, rated 50/60 Hz, 3363 kVA max continuous rating, 3699.3 kVA max limited duty (2‑hour) overload rating, maximum ambient temperature 27ºC or 40 C, Class H.

Model(s)
Frame S7

Notes:
1. The complete designation consists of the frame size, as detailed above, followed by other figures indicating number of poles, number of bearings and a letter indicating core length.
2. Generators may be fitted with anti-condensation heaters and/or temperature detectors.

To the requirements of
CSA C22.2 No. 100-14+Upd.1 (Seventh Edition)(R2019)

Three phase synchronous generators, guarded or drip‑proof

Model(s)Input Power (kVA)Power FactorVoltage (kVAC)Insulation Class Ambient Temp (°C max)Pole(s)Frequency (Hz)
Type DIG1423760 to 6700 0.83.3 to 13.8F40450 or 60

Note: Without any change to the rated Ins. class of products  Class F(155°C) , an Insulation system class H(180°C), may be used; refer to descriptive report for details on system and materials adopted as alternative.

To the requirements of
CSA C22.2 No. 100-14 (Upd.1 April 2017)(Seventh Edition) (R2019)

Synchronous generators Type P80, rotating field, brushless, self‑excited, guarded or drip‑proof, Class H for ratings up to 4160V and Class F for ratings over 4160V.

Model(s)Voltage (V min)Voltage (V max)Power (kVA max)Power (kW max)Power FactorFrequency (Hz)Ambient Temp (°C)
LVSI804, HVSI804, MVSI80438013800519041520.850 / 6040

Notes:
1. The complete type designation consists of the frame size as detailed above, followed by other figures and a letter indicating the core length; R, S, T, W, X or Y.
2. Generators may be fitted with anti-condensation heaters, resistance temperature detectors or thermistors.


Synchronous generators, brushless, self‑excited, form wound, drip‑proof guarded, 3‑ph, 5250kVA max continuous, 0.8 power factor, 13,800Vac max, 4‑pole, 50/60 Hz, 27°C or 40°C maximum ambient, Class H.

Model(s)
S9

Notes:

  1. The model designation S9 (consists of the frame size) shall be followed by other numbers and letters indicating voltage, number of poles, number of bearings, and a letter indicating core length.
  2. Generators may be operated at 10% overload for 2-hours in a 24-hour period (if machine marked).

To the requirements of
CSA C22.2 No. 100-14 (Upd.1 April 2017)(Seventh Edition) (R2019)

Synchronous generators, brushless, self‑excited, drip‑proof, three phases, 4‑pole, Class H.

Model(s)Voltage Load (VAC max)Power (kVA max)Frequency (Hz)Ambient Temp (°C)Current (A max)
S9L1380‑4805100 continuous / 5455 max overload 2hrs 50 or 60406135 continuous / 6567 max overload

Notes: 

1. The complete designation consists of the frame size, as detailed above, followed by other figures indicating number of poles, number of bearings and a letter indicating core length. 
2. The generators may be supplied without terminal boxes for incorporating in generating sets, subject to the acceptability of the combination by CSA Group. 
3. Generators may be fitted with anti-condensation heaters and/or temperature detectors.