IEC 60287-1-2:2023
Electric cables - Calculation of the current rating - Part 1-2: Current rating equations (100 % load factor) and calculations of losses - Sheath eddy current loss factors for two circuits in flat formation
Product Details
The method descibed in this document provides coefficients which are applied as corrections to the loss factors for the sheaths of one isolated three-phase circuit. These corrections are negligible for cables where the parameter m is less than approximately 0,1 (m = ?/(Rs · 107)), which corresponds to a sheath longitudinal resistance higher than 314 µO/m at 50 Hz.
Consequently, the method is used for most sizes of aluminium-sheathed cables, but is not required for lead-sheathed cables unless they are unusually large.
The coefficients are provided in tabular form and have been computed from fundamental formulae for sheath losses, the evaluation of which calls for expertise in computer programming which will possibly not be readily available in general commercial situations. The development of simplified formulae for some of the tabulated coefficients is under consideration.
Losses for cables in a single circuit is covered in IEC 60287-1-1.