Overview

Expanded Recall: Kidde Recalls Residential Smoke Alarms and Combination Smoke/CO Alarms

Toronto,

The September 11, 2014 recall involves Kidde branded AC/DC powered residential smoke alarms and combination smoke/CO alarms, models KN-COSM-IBACA, i12010S-CO-CA and i12010S-CA. This recall has been expanded to include one additional date code of model i12010S-CO-CA alarm.

Should a power outage occur at the same second that the device is performing a once-per-minute sensor health check, the device may go into a “latched” mode, causing it not to alarm in the presence of smoke and/or carbon monoxide. An affected device will sound if it receives a signal from an alarm in the same interconnected system. Once power is restored, a latched device will sound an alarm regardless of the presence of smoke and/or carbon monoxide.

Health Canada (HC):
http://healthycanadians.gc.ca/recall-alert-rappel-avis/hc-sc/2015/54652r-eng.php#!prettyPhoto

À propos du Groupe CSA

Le Groupe CSA est une association indépendante sans but lucratif, constituée de membres et dédiée à la sécurité, au bien social et à la durabilité. Nous sommes une organisation accréditée au niveau international spécialisée dans le  développement des normes ainsi que l’évaluation et la certification des produits. Nous fournissons aussi des services de formation et d’éducation ainsi que d’évaluation des produits de consommation. Nous possédons un large spectre de connaissances et de compétences qui comprend les équipements industriels, le secteur de la construction et de la plomberie, les soins de santé et le domaine électromédical, les appareils ménagers et le gaz, les énergies de remplacement,  les systèmes d’éclairage et  les énergies renouvelables. La marque CSA figure sur des milliards de produits partout dans le monde.

Communiquer avec nous

Allison Hawkins
Responsable des affaires institutionnelles
Groupe CSA
416-747-2615
[email protected]